Ductwork. Fabricate ductwork from a minimum 24-gauge zinc-coated (galvanized) steel, lock forming quality sheets conforming to ASTM A527. Zinc coating thickness: “Commercial” class G90, except a minimum of 2 oz. Per sq. ft. where the metal is exposed to the weather. Duct Accessories: Fire dampers shall be installed in all locations as required by building code. Diffusers shall be of the following type and sized to meet demand:

Appears in 22 contracts

Samples: Lease Agreement, Lease Agreement, Lease Agreement

Ductwork. Fabricate ductwork from a minimum 24-24 gauge zinc-coated (galvanized) steel, lock lock-forming quality sheets conforming to ASTM A527. Zinc coating thickness: “Commercial” class Class G90, except a minimum of 2 oz. Per per sq. ft. where the metal is exposed to the weather. Duct Accessories: Fire dampers shall be installed in all locations as required by building codelocations. Diffusers shall be of the following type and sized to meet demand:

Appears in 2 contracts

Samples: Lease Agreement, Lease Agreement