Electrical Items. All Accommodation shall meet the following standards: 3.10.1 all Accommodation shall have a current NICEIC or NAPIT electrical safety report. This report must have no items marked as requiring urgent attention or investigation; 3.10.2 all electrical wiring shall be covered; 3.10.3 all surface mounted wiring shall be enclosed in suitable plastic conduit; 3.10.4 all RCD consumer unit shall be housed in a cupboard, with a childproof latch on the door to prevent access and ensure that cables under the meter are covered; 3.10.5 xxxxxx and cooker. Fused spurs shall be provided; 3.10.6 Portable Appliance Testing (PAT) is required annually for all electrical appliance supplied (e.g. electric cookers); 3.10.7 an adequate number of sockets shall be required and the following shall be appropriately spaced: (a) living room. Two double sockets as a minimum; (b) double bedrooms. Two double sockets as a minimum; (c) single bedrooms. One double socket as a minimum; (d) kitchen. Two double sockets at worktop height as a minimum, one socket for a fridge and one socket for a washing machine; (e) landing. One socket as a minimum; 3.10.8 electric lighting in each room is to be of sufficient intensity.
Appears in 3 contracts
Samples: Capital Grant Agreement, Capital Grant Agreement, Capital Grant Agreement
Electrical Items. All Accommodation accommodation shall meet the following standards:
3.10.1 all Accommodation accommodation shall have a current NICEIC or NAPIT electrical safety report. This report must have no items marked as requiring urgent attention or investigation;
3.10.2 all electrical wiring shall be covered;
3.10.3 all surface mounted wiring shall be enclosed in suitable plastic conduit;
3.10.4 all RCD consumer unit shall be housed in a cupboard, with a childproof latch on the door to prevent access and ensure that cables under the meter are covered;
3.10.5 xxxxxx boiler and cooker. Fused spurs shall be provided;
3.10.6 Portable Appliance Testing (PATXXX) is required annually for all electrical appliance supplied (e.g. electric cookers);
3.10.7 an adequate number of sockets shall be required and the following shall be appropriately spaced:
(a) living room. Two 2 double sockets as a minimum;
(b) double bedrooms. Two 2 double sockets as a minimum;
(c) single bedrooms. One 1 double socket as a minimum;
(d) kitchen. Two 2 double sockets at worktop height as a minimum, one 1 socket for a fridge and one socket for a washing machine;
(e) landing. One 1 socket as a minimum;
3.10.8 electric lighting in each room is to be of sufficient intensity.
Appears in 2 contracts
Samples: Revenue Funding Agreement, Revenue Funding Agreement
Electrical Items. All Accommodation shall meet the following standards:
3.10.1 all Accommodation shall have a current NICEIC or NAPIT electrical safety report. This report must have no items marked as requiring urgent attention or investigation;
3.10.2 all electrical wiring shall be covered;
3.10.3 all surface mounted wiring shall be enclosed in suitable plastic conduit;
3.10.4 all RCD consumer unit shall be housed in a cupboard, with a childproof latch on the door to prevent access and ensure that cables under the meter are covered;
3.10.5 xxxxxx and cooker. Fused spurs shall be provided;
3.10.6 Portable Appliance Testing (PAT) is required annually for all electrical appliance supplied (e.g. electric cookers);
3.10.7 an adequate number of sockets shall be required and the following shall be appropriately spaced:
(a) living room. Two 2 double sockets as a minimum;
(b) double bedrooms. Two 2 double sockets as a minimum;
(c) single bedrooms. One 1 double socket as a minimum;
(d) kitchen. Two 2 double sockets at worktop height as a minimum, one 1 socket for a fridge and one socket for a washing machine;
(e) landing. One 1 socket as a minimum;
3.10.8 electric lighting in each room is to be of sufficient intensity.