Common use of NYISO Coordination Clause in Contracts

NYISO Coordination. All testing shall be coordinated with the NYISO and CHGE to ensure grid conditions are available for testing conditions. Unity power factor shall be tested (power factor must be one to conduct the test) unless otherwise specified by NYISO or utility practices. Storage Rating Test Sequencing: Storage Capacity Rating Test and Round-Trip Efficiency Test: STEP 1: Precharging Storage prior to Storage Capacity Rating Test. To commence a Storage Capacity Rating test the Project must be charged to 100% Usable SOC.

Appears in 2 contracts

Samples: Energy Storage Services Agreement, Storage Services Agreement

AutoNDA by SimpleDocs

NYISO Coordination. All testing shall be coordinated with the NYISO and CHGE NYSEG to ensure grid conditions are available for testing conditions. Unity power factor shall be tested (power factor must be one to conduct the test) unless otherwise specified by NYISO or utility practices. Storage Rating Test Sequencing: Storage Capacity Rating Test and Round-Trip Efficiency Test: STEP 1: Precharging Storage prior to Storage Capacity Rating Test. To commence a Storage Capacity Rating test the Project must be charged to 100% Usable SOC.

Appears in 1 contract

Samples: Storage Services Agreement

AutoNDA by SimpleDocs

NYISO Coordination. All testing shall be coordinated with the NYISO and CHGE RG&E to ensure grid conditions are available for testing conditions. Unity power factor shall be tested (power factor must be one to conduct the test) unless otherwise specified by NYISO or utility practices. Storage Rating Test Sequencing: Storage Capacity Rating Test and Round-Trip Efficiency Test: STEP 1: Precharging Storage prior to Storage Capacity Rating Test. To commence a Storage Capacity Rating test the Project must be charged to 100% Usable SOC.

Appears in 1 contract

Samples: Storage Services Agreement