Performance test settings Sample Clauses

Performance test settings. Before utilising Hyperledger Caliper [11] for conducting a perfor- xxxxx analysis on the prototype, custom benchmark tests had to be created. These tests are set up to initialise the ledger (adding the medical supply), perform the transaction (e.g. requests) and afterwards clear the ledger (deleting the medical supply). All transactions are set to run for a total length of a minute each and have five workers run concurrently invoking the transactions. By setting these with a time limit, information can be gathered on the latency and the number of transactions invoked. Hyperledger Caliper has been run a total of five times where the averages of the measurements were taken and put in table 2. Average results were taken for accuracy reasons, where the total amount of testing runs to be used was done up to five, as otherwise it would become too computationally intensive for the machine it was run on. It should be noted that during testing, due to high load the transactions querying multiple entries from the ledger could not manage to finish in time resulting in time-out errors. Re-running these individually, instead of all at once, was done for it to resolve this issue. Function Name Amount invoked Send Rate Max Latency (s) Min Latency (s) Avg Latency (s) Through put Issue 1,120 18.8 1.14 0.10 0.35 18.8 Request 21,181 358.0 0.08 0.01 0.02 357.0 CancelRequest 22,095 374.4 0.08 0.01 0.02 374.4 ApproveRequest 19,664 333.1 0.11 0.01 0.02 333.1 RejectRequest 22,357 378.8 0.09 0.01 0.02 378.7 CheckHistory 3,549 60.1 0.23 0.02 0.10 60.0 CheckUserHistory 2,945 49.8 0.40 0.03 0.12 49.7 CheckAvailableMedicine 3,270 55.2 0.36 0.03 0.11 55.2 CheckRequestedMedicine 3,181 53.7 0.29 0.03 0.13 53.5 SearchMedicineByName 5,260 53.6 0.22 0.03 0.07 53.3 ChangeStatus 21,242 359.9 0.08 0.01 0.02 359.9 ChangeHolder 21,102 357.6 0.07 0.01 0.02 357.5 Table 2: Average performance results over five runs before the TPM integration Prototype before TPM changes. From table 2 it can be seen that each transaction is relatively fast with the highest latency being around an average of 6.39 seconds. A distinction can be made between transactions that have a high amount of being invoked with lower latency and transactions that are the opposite with a low amount of being invoked and higher latency. This is to be expected as the latter is the type of transaction that queries all entries from the ledger and filters on certain criteria (e.g. on only available medical supply). The Issue transaction i...
AutoNDA by SimpleDocs

Related to Performance test settings

  • Acceptance/Performance Test 4.7.1 Prior to synchronization of the Power Project, the SPD shall be required to get the Project certified for the requisite acceptance/performance test as may be laid down by Central Electricity Authority or an agency identified by the central government to carry out testing and certification for the solar power projects.

  • Performance Testing 7.2.1 The Design-Builder shall direct and supervise the tests and, if necessary, the retests of the Plant using Design-Builder’s supervisory personnel and the Air Emissions Tester shall conduct the air emissions test, in each case, in accordance with the testing procedures set forth in Exhibit A (the “Performance Tests”), to demonstrate, at a minimum, compliance with the Performance Guarantee Criteria. Owner is responsible for obtaining Air Emissions Tester and for ensuring Air Emissions Tester’s timely performance. Design-Builder shall cooperate with the Air Emissions Tester to facilitate performance of all air emissions tests. Design-Builder shall not be held responsible for the actions of Owner’s employees and third parties involved in the Performance Testing, including but not limited to Air Emissions Tester.

  • Power Factor Design Criteria (Reactive Power A wind generating plant shall maintain a power factor within the range of 0.95 leading to 0.95 lagging, measured at the Point of Interconnection as defined in this LGIA, if the ISO’s System Reliability Impact Study shows that such a requirement is necessary to ensure safety or reliability. The power factor range standards can be met using, for example without limitation, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors if agreed to by the Connecting Transmission Owner for the Transmission District to which the wind generating plant will be interconnected, or a combination of the two. The Developer shall not disable power factor equipment while the wind plant is in operation. Wind plants shall also be able to provide sufficient dynamic voltage support in lieu of the power system stabilizer and automatic voltage regulation at the generator excitation system if the System Reliability Impact Study shows this to be required for system safety or reliability.

  • Mileage Measurement Where required, the mileage measurement for LIS rate elements is determined in the same manner as the mileage measurement for V&H methodology as outlined in NECA Tariff No. 4.

  • ACCEPTANCE TESTS 11.1 If the Contract provides acceptance tests for Goods and/or the result of Services after their completion and/or delivery to the Purchaser, the acceptance shall only be considered as definitive when such tests have demonstrated the compliance of the Goods and/or the result of the Services to the requirements in the Contract.

  • Registry Performance Specifications Registry Performance Specifications for operation of the TLD will be as set forth in Specification 10 attached hereto (“Specification 10”). Registry Operator shall comply with such Performance Specifications and, for a period of at least one (1) year, shall keep technical and operational records sufficient to evidence compliance with such specifications for each calendar year during the Term.

  • Acceptance Testing At the time of installation of a LIS trunk group, and at no additional charge, acceptance tests will be performed to ensure that the service is operational and meets the applicable technical parameters.

  • PERFORMANCE MANAGEMENT SYSTEM 5.1 The Employee agrees to participate in the performance management system that the Employer adopts or introduces for the Employer, management and municipal staff of the Employer.

  • Power Factor Design Criteria Developer shall design the Large Generating Facility to maintain an effective power delivery at demonstrated maximum net capability at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all generators in the New York Control Area on a comparable basis. The Developer shall design and maintain the plant auxiliary systems to operate safely throughout the entire real and reactive power design range. The Connecting Transmission Owner shall not unreasonably restrict or condition the reactive power production or absorption of the Large Generating Facility in accordance with Good Utility Practice.

  • Standard Service Features Ethernet Access allows Customer to terminate single and/or multiple Ethernet Virtual Circuits (EVCs) from Customer equipment onto a single Ethernet Access UNI.

Time is Money Join Law Insider Premium to draft better contracts faster.