Power Quality Standards. The Generator must demonstrate its compliance with the following power quality requirements:
Power Quality Standards. The Generator must demonstrate its compliance with the following power quality requirements: Voltage & Voltage Regulation: The Generator's Facility shall not adversely affect the voltage and voltage regulation on any part of the Wire Owner's Facilities. At the Point of Interconnection, the Generator's three-phase voltages must conform to CSA CAN3-C235-83. Harmonics: The Generator must not cause an unacceptable level of harmonics during operation of the Generator's Facility. Limits on acceptable voltage and current distortion, telephone interference limits, measurement approaches and mitigation suggestions are detailed in the attached Harmonic Specification For Harmonic Producing Customers Connected to the UtiliCorp Networks Canada System, which is included as Appendix B to this Schedule. Voltage Fluctuations: The Generator must not cause an unacceptable level of voltage fluctuation during starting, operation, or shutdown of the Generator's Facility. The Wire Owner's standard on voltage flicker limits are shown in the Voltage Flicker Limits Chart that is included as Appendix C to this Schedule.