Common use of Revenue Metering Clause in Contracts

Revenue Metering. The Connecting Transmission Owner’s revenue metering shall be located at the North Country Solar Collector Station on the generator side of the 48.3kV breaker in accordance with the requirements identified in the Project Specific Specifications, and shall consist of: • two (2) current transformers (“CTs”), GE type JKW-250ER; • two (2) voltage transformers (“VTs”), GE type JVT-250; and • one (1) revenue meter. (Note: The Connecting Transmission Owner’s revenue metering CTs and VTs cannot be used to feed the Interconnection Customer’s check meter.) The Interconnection Customer shall install a meter panel in accordance with the Project Specific Specifications and the Connecting Transmission Owner’s Electric System Bulletins (“ESBs”) 756A. The Connecting Transmission Owner will provide the CTs and VTs, and the Interconnection Customer shall mount them, make grounding connections, and complete all primary wiring. In addition, the Connecting Transmission Owner shall provide the meter socket enclosure for the Interconnection Customer to install near the Connecting Transmission Owner’s XXX.