Common use of Synchronous Generation Clause in Contracts

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 210 contracts

Samples: Service Agreement, Service Agreement, Service Agreement

AutoNDA by SimpleDocs

Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 11 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 10 contracts

Samples: Agreement, Agreement, Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.

Appears in 10 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Connecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 8 contracts

Samples: Service Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.

Appears in 5 contracts

Samples: Service Agreement, Service Agreement, Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a with dynamic reactive capability over the power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO System Operator or the Interconnecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated synchronous (and non-wind non-synchronous generators as specified in Appendix G, Section A.ii.4, to the New York Control Area or Transmission District (as applicableLGIA) generators on a comparable basis, basis and in accordance with Good Utility PracticeOperating Requirements.

Appears in 4 contracts

Samples: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 4 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a with dynamic reactive capability over the power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO System Operator or the Interconnecting Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated synchronous (and non-wind non- synchronous generators as specified in Appendix G, Section A.ii.4, to the New York Control Area or Transmission District (as applicableLGIA) generators on a comparable basis, basis and in accordance with Good Utility PracticeOperating Requirements.

Appears in 3 contracts

Samples: Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice. The requirements of this paragraph shall not apply to wind generators.

Appears in 3 contracts

Samples: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Study Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 0.90 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 3 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.

Appears in 3 contracts

Samples: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating the Facility to maintain a effective composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, lagging unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. Interconnection Customer shall design and maintain the plant auxiliary systems to operate safely throughout the entire real and reactive power design range.

Appears in 3 contracts

Samples: Interconnection Agreement, Standard Interconnection Agreement, Standard Interconnection Agreement

AutoNDA by SimpleDocs

Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. The requirements of Appendix G to this LGIA shall apply to wind generators.

Appears in 2 contracts

Samples: Agreement, Large Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery deliver at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 2 contracts

Samples: Surplus Large Generator Interconnection Agreement, Surplus Large Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.. 41

Appears in 1 contract

Samples: Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small synchronous Generating Facility to maintain be capable of providing a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Provider has established different requirements that apply to all similarly situated synchronous generators in connected to the New York Control Area or Transmission District (as applicable) Provider’s Transmission System on a comparable basis, in accordance with Good Utility Practice.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of established byof 0.95 leading to 0.95 lagging, unless the NYISO ConnectingNYISO or the Transmission Owner in on a comparable basis, until NYISOin whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

Appears in 1 contract

Samples: Service Agreement

Synchronous Generation. The Interconnection Customer shall design its designits Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects Distribution Provider has established different requirements that apply to all similarly situated synchronous generators in the New York Control Area or Transmission District (as applicable) control area on a comparable basis, in accordance with Good Utility Practice.

Appears in 1 contract

Samples: Small Generator Interconnection Agreement

Synchronous Generation. The Interconnection Customer shall design its Small the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects IPA has established different requirements that apply to all similarly situated generators in connecting to the New York Control Area or Transmission District (as applicable) IPP Switchyard on a comparable basis, in accordance with Good Utility Practicecomparablebasis.

Appears in 1 contract

Samples: Generator Interconnection Agreement