Synchronous Generation. Interconnection Customer shall design the Generating Facility to be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at all power factors over 0.95 leading to 0.95 lagging, unless the Transmission Provider has established different requirements that apply to all synchronous generators in the Local Balancing Authority on a comparable basis. The applicable Local Balancing Authority power factor requirements are listed on the Transmission Provider’s website at xxxxx://xxx.xxxxxxxxxx.xxx/Library/Repository/Study/Generator%20Interco nnection/Reactive%20Generator%20Requirements.pdf and may be referenced in the Appendices to this GIA. The Generating Facility shall be capable of continuous dynamic operation throughout the power factor design range as measured at the Point of Interconnection. Such operation shall account for the net effect of all energy production devices on the Interconnection Customer’s side of the Point of Interconnection.
Appears in 10 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Synchronous Generation. Interconnection Customer shall design the Generating Facility to be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at all power factors over 0.95 leading to 0.95 lagging, unless the Transmission Provider has established different requirements that apply to all synchronous generators in the Local Balancing Authority on a comparable basis. The applicable Local Balancing Authority power factor requirements are listed on the Transmission Provider’s website at xxxxx://xxx.xxxxxxxxxx.xxx/Library/Repository/Study/Generator%20Interco nnectionxxxxx://xxx.xxxxxxxxxx.xxx/Library/Repository/Study/Generator%20Interconnec tion/Reactive%20Generator%20Requirements.pdf and may be referenced in the Appendices to this GIA. The Generating Facility shall be capable of continuous dynamic operation throughout the power factor design range as measured at the Point of Interconnection. Such operation shall account for the net effect of all energy production devices on the Interconnection Customer’s side of the Point of Interconnection.
Appears in 3 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Interconnection Agreement
Synchronous Generation. Interconnection Customer shall design the Generating Facility to be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at all power factors over 0.95 leading to 0.95 lagging, unless the Transmission Provider has established different requirements that apply to all synchronous generators in the Local Balancing Authority on a comparable basis. The applicable Local Balancing Authority power factor requirements are listed on the Transmission Provider’s website at xxxxx://xxx.xxxxxxxxxx.xxx/Library/Repository/Study/Generator%20Interco nnectionxxxxx://xxx.xxxxxxxxxx.xxx/Library/Repository/Study/Generator%20Interc onnection/Reactive%20Generator%20Requirements.pdf and may be referenced in the Appendices to this GIA. The Generating Facility shall be capable of continuous dynamic operation throughout the power factor design range as measured at the Point of Interconnection. Such operation shall account for the net effect of all energy production devices on the Interconnection Customer’s side of the Point of Interconnection.
Appears in 2 contracts
Samples: Interconnection Agreement, Generator Interconnection Agreement