Synchronous Generation. Applicant shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor of 0.95 or less leading, or a power factor of 0.95 or less lagging, unless the GTC has established different requirements that apply to all synchronous generators in the Control Area on a comparable basis. This power factor range shall be dynamic.
Appears in 3 contracts
Samples: Interconnection and Operation and Maintenance Agreement, Interconnection and Operation and Maintenance Agreement, Interconnection and Operation and Maintenance Agreement
Synchronous Generation. Applicant Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 or less leading, or a power factor of leading to 0.95 or less lagging, unless the GTC Grant PUD has established different requirements that apply to all synchronous generators in the Control Balancing Authority Area on a comparable basis. This power factor range shall be dynamic.
Appears in 2 contracts
Samples: Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia)
Synchronous Generation. Applicant Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor of between 0.95 or less leading, or a power factor of 0.95 or less laggingto 1.00, unless the GTC Grant PUD has established different requirements that apply to all synchronous generators in the Control Balancing Authority Area on a comparable basis. This power factor range shall be dynamic.
Appears in 1 contract
Samples: Interconnection Agreement