Common use of Testing of Metering Equipment Clause in Contracts

Testing of Metering Equipment. Connecting Transmission Owner shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipment. If requested to do so by RG&E, Connecting Transmission Owner shall, at RG&E’s expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner shall give reasonable notice of the time when any inspection or test shall take place, and RG&E may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&E’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&E’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half the time from the date of the last previous test of the Metering Equipment.

Appears in 1 contract

Samples: Transmission Facility Interconnection Agreement

AutoNDA by SimpleDocs

Testing of Metering Equipment. Connecting Transmission Owner OwnerCon Edison shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Developer, Connecting Transmission Owner Owner, Con Edison shall, at RG&E’s Developer’sits expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner OwnerCon Edison shall give reasonable notice of the time when any inspection or test shall take place, and RG&E DeveloperCon Edison and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EDeveloper’sCon Edison’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. .. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner OwnerCon Edison shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the. If the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one- half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on the Developer’s or Connecting Transmission Owner’sCon Edison’s property at any time.

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

Testing of Metering Equipment. Connecting Transmission Owner shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Developer, Connecting Transmission Owner shall, at RG&EDeveloper’s expense, inspect or 30 SERVICE AGREEMENT NO. 2341 test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Developer and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EDeveloper’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on the Developer’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Service Agreement

Testing of Metering Equipment. Connecting Transmission Owner OwnerTrAILCo shall inspect and test all of its itsthe Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Developer, Connecting Transmission Owner shall, at RG&EDeveloper’s expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner in accordance with applicable NYISO requirements. TrAILCo shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Developer and NYISONYSEG may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EDeveloperthe owner’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission OwnerOwnerTrAILCo’s failure to maintain, then Connecting Transmission Owner OwnerTrAILCo shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner Ownerthe range set forth in the applicable NYISO or PJM standard, TrAILCo shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloperthe other Party’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one- half the time from the date of the last previous test of the Metering Equipment.. The NYISO shall reservereserves the right to review all associated metering equipment installation on the Developer’s or Connecting Transmission Ownerinspect all Metering Equipment installed on NYSEG’s or TrAILCo’s property at any timereasonable times and upon reasonable notice to

Appears in 1 contract

Samples: Standard Large Generator Transmission Facility Interconnection Agreement

Testing of Metering Equipment. Connecting Transmission Owner OwnerDeveloper shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO orrequired by ISO Procedures, Transmission Developer, Connecting Transmission Owner shall, at RG&E’s Developer’sits own expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner OwnerDeveloper shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Developer and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&ETransmission Developer’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. Transmission Developer and NYISO shall address the loss of meter data or meter data anomalies in accordance with ISO Procedures. The NYISO shall reserve the right to review all associated metering equipment installation on the Transmission Developer’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

Testing of Metering Equipment. Connecting Transmission Owner shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Interconnection CustomerDeveloper, Connecting Transmission Owner shall, at RG&EInterconnection Customer’sDeveloper’s expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Interconnection CustomerDeveloper and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EInterconnection Customer’sDeveloper’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EInterconnection Customer’sDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on the Interconnection Customer’sDeveloper’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Interconnection Agreement

Testing of Metering Equipment. Connecting Transmission Owner OwnerCon Edison shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Developer, Connecting Transmission Owner Owner, Con Edison shall, at RG&E’s Developer’sits expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner OwnerCon Edison shall give reasonable notice of the time when any inspection or test shall take place, and RG&E DeveloperCon Edison and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EDeveloper’sCon Edison’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. .. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner OwnerCon Edison shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the. If the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one- half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on the Developer’s or Connecting Transmission Owner’sCon Xxxxxx’s property at any time.

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

AutoNDA by SimpleDocs

Testing of Metering Equipment. Connecting Transmission Owner shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Interconnection CustomerDeveloper, Connecting Transmission Owner shall, at RG&EInterconnection CustomerDeveloper’s expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Interconnection CustomerDeveloper and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EInterconnection CustomerDeveloper’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EInterconnection CustomerDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on Interconnection Customerthe Developer’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Class Year Cluster Study Agreement

Testing of Metering Equipment. Connecting Transmission Owner OwnerDeveloper shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO orrequired by ISO Procedures, Transmission Developer, Connecting Transmission Owner shall, at RG&E’s Developer’sits own expense, inspect or test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner OwnerDeveloper shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Developer and NYISO and Connecting Transmission Owner may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&ETransmission Developer’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. Transmission Developer and NYISO shall address the loss of meter data or meter data anomalies in accordance with ISO Procedures. The NYISO shall reserve the right to review all associated metering equipment installation on the Transmission Developer’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

Testing of Metering Equipment. Connecting Transmission Owner shall inspect and test all of its Metering Equipment upon installation and at least once every two (2) years thereafter for metering accuracy test and inspection of metering equipmentthereafter. If requested to do so by RG&ENYISO or Developer, Connecting Transmission Owner shall, at RG&EDeveloper’s expense, inspect or 30 SERVICE AGREEMENT NO. 2356 test Metering Equipment more frequently than every two (2) years. Connecting Transmission Owner shall give reasonable notice of the time when any inspection or test shall take place, and RG&E Developer and NYISO may have representatives present at the test or inspection. If at any time Metering Equipment is found to be inaccurate or defective, it shall be adjusted, repaired or replaced at RG&EDeveloper’s expense, in order to provide accurate metering, unless the inaccuracy or defect is due to Connecting Transmission Owner’s failure to maintain, then Connecting Transmission Owner shall pay. If Metering Equipment fails to register, or if the measurement made by Metering Equipment during a test varies by more than two percent from the measurement made by the standard meter used in the test, Connecting Transmission Owner shall adjust the measurements by correcting all measurements for the period during which Metering Equipment was in error by using RG&EDeveloper’s check meters, if installed. If no such check meters are installed or if the period cannot be reasonably ascertained, the adjustment shall be for the period immediately preceding the test of the Metering Equipment equal to one‐half one-half the time from the date of the last previous test of the Metering Equipment. The NYISO shall reserve the right to review all associated metering equipment installation on the Developer’s or Connecting Transmission Owner’s property at any time.

Appears in 1 contract

Samples: Lgia