Voltage transformers. (A) The primary winding of VTs must be connected to the circuits being measured. (B) The secondary windings of VTs for Type 1, 2 and 3 Meters must meet the following criteria: Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage 1 IEC 61869-3 0.2 2 VTs (or 1 VT with two (2) or more secondary windings) 1 VT secondary winding dedicated to the Main Meter for CfD Settlement Activities purposes only. Check Meter VTs can be used for other purposes provided that such Check VT Meters comply with the accuracy requirements in paragraph 2.2 of these TSRs.
Appears in 4 contracts
Samples: Private Network CFD Agreement, Private Network CFD Agreement, Private Network CFD Agreement
Voltage transformers. (A) The primary winding of VTs must be connected to the circuits being measured.
(B) The secondary windings of VTs for Type 1, 2 and 3 Meters must meet the following criteria: Type of Meter Relevant Standard Minimum Class Accuracy No. of sets Usage 1 IEC 61869-3 0.2 2 VTs (or 1 VT with two (2) or more secondary windings) 1 VT secondary winding dedicated to the Main Meter for CfD Settlement Activities purposes only. Check Meter VTs can be used for other purposes provided that such Check VT Meters comply with the accuracy requirements in paragraph 2.2 of these TSRs.