Seller shall likewise exercise all reasonable efforts to provide prior notice to CEB of all unscheduled openings of the interconnection with the CEB System and all unscheduled complete or partial outages of the Facility and, where prior notice is not given, shall promptly notify CEB of all such openings of the interconnection and all such partial or complete outages of the Facility.
In the circumstances specified in Paragraphs 1.4.1(a) and 1.4.1(b) of this Part 4, and provided that the conditions referred to therein are not caused by circumstances attributable to CEB or the CEB System, the Facility shall not be available for the purposes of this Agreement and Seller shall declare the Reported Availability of the Facility accordingly by issuing a Notice of Revised Availability.
The Facility shall be capable of contributing to voltage control by continuous changes to the reactive power supplied to the CEB System.
Voltage Fluctuations Seller shall ensure that the connection of the Facility to the CEB System does not result in the level of fluctuation of the supply voltage on the CEB System at the Interconnection Boundary, measured at the Point of Delivery, exceeding limits set out below.
The Facility must be capable of remaining connected at or below the limit in Figure 2 for any CEB System conditions.
A different LVRT curve may be required by the CEB, to ensure the CEB System reliability and security.
Low Voltage Ride Through Capability In addition to remaining connected to the CEB System, the Facility shall have the technical capability to provide the following: During the CEB System voltage dip each inverter of the Facility shall provide active power in proportion to retained voltage and maximise reactive current to the CEB System without exceeding the inverter Limit.
The maximisation of reactive current shall continue until the CEB System voltage recovers to within the normal operational range of the CEB System.
The Facility’s Substation transformer shall be designed such that the Facility capability shall be possible over the full range of CEB System voltages specified in Part 3 of this Schedule.
The weekly 95 percentile of Phase (Voltage) Unbalance, calculated in accordance with IEC61000-4-30 and IEC61000-3-13, on the CEB System shall be less than or equal to 1.3% unless abnormal conditions prevail.