Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation control room to Power Plant Control room/SAS room/DCS room. a) Fiber optic Type- Single mode (9/125µm) b) Connector type- FC/PC in ODF, LC/PC in Equipment. c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substation's existing SDH & PDH for: a) Voice communication (2-wire & IP telephony both). b) RTU/SAS/DCS Communication (IEC-104 Protocol) c) Tele protection. d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 2 contracts
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka Baraiyarhat substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka Baraiyarhat substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka Baraiyarhat substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 2 contracts
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Xxx'x Bazar Grid Substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationXxx'x Bazar Grid Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
) c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension GIS BAY of Bhaluka substation Xxx'x Bazar Grid Substation need to be integrated to NLDC Master Station &. & Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 2 contracts
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka Chuadanga substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka Chuadanga substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka Chuadanga substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 2 contracts
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Kachua Grid Substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationKachua Grid Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
) c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka substation Kachua Grid Substation need to be integrated to NLDC Master Station &. & Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 2 contracts
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Xxx'x Bazar Substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationXxx'x Bazar Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension GIS BAY of Bhaluka substation Xxx'x Bazar Substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Power Purchase Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Kachua Substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationKachua Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka substation Kachua Substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Power Purchase Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Chandpur Substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationChandpur Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka substation Chandpur Substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Power Purchase Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Mongla 132/33 kV Grid Substation, Bagerhat or Gollamari 132/33 kV Grid Substation, Khulna control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka substationMongla 132/33 kV Grid Substation, Bagerhat's existing or Gollamari 132/33 kV Grid Substation, Khulna's SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
) c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension GIS BAY of Bhaluka substation Mongla 132/33 kV Grid Substation, Bagerhat or Gollamari 132/33 kV Grid Substation, Khulna need to be integrated to NLDC Master Station &. & Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Implementation Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka Netrokona substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka Netrokona substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka Netrokona substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Implementation Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka Chandraghona substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to be connected with Bhaluka Chandraghona substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka Chandraghona substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Implementation Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka substation Mongla 132/33 kV Grid Substation, Bagerhat or Gollamari 132/33 kV Grid Substation, Khulna control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and an d those to be connected with Bhaluka substationMongla, Bagerhat/Gollamari, Khulna Substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension GIS BAY of Bhaluka substation Mongla 132/33 kV Grid Substation, Bagerhat or Gollamari 132/33 kV Grid Substation, Khulna need to be integrated to NLDC Master Station &. Back-Back- up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Power Purchase Agreement
Communication System. The Company shall provide the Communication/SCADA-EMS facilities to proposed solar power plant; the power plant authority shall ensure the followings- Optical Fiber connectivity from Bhaluka Chandraghona substation control room to Power Plant Control room/SAS room/DCS room.
a) Fiber optic Type- Single mode (9/125µm)
b) Connector type- FC/PC in ODF, LC/PC in Equipment.
c) Nos of optical Core (ODF to ODF) -24. Optical Multiplexer SDH & PDH shall be installed in power plant and those to t o be connected with Bhaluka Chandraghona substation's existing SDH & PDH for:
a) Voice communication (2-wire & IP telephony both).
b) RTU/SAS/DCS Communication (IEC-104 Protocol)
c) Tele protection.
d) LAN Services (Video Conferencing, CC Camera Central Monitoring, DFDR central monitoring etc.) Power Plant's SDH & PDH need to be integrated with existing Telecom NMS (FOXMAN/U2000). Power Plant RTUs/SAS/DCS and extension BAY of Bhaluka Chandraghona substation need to be integrated to NLDC Master Station &. Back-up Station as per approved signal list and configuration parameters from PGCB SCADA Division.
Appears in 1 contract
Samples: Power Purchase Agreement