Common use of CONTROLLED ENVIRONMENT Clause in Contracts

CONTROLLED ENVIRONMENT. Forced under floor air cooling will be supplied through strategically placed vented tiles throughout the data hall. Cooled air will, as standard, be supplied to the front of the rack. Average data hall return air temperature is measured at Ingress points above the air conditioning units and will be 24 degrees Centigrade within a tolerance of plus or minus 2 degrees Centigrade. Humidity will be maintained at 50% within a tolerance of plus or minus 10%.

Appears in 5 contracts