Correction of Rated Continuous Current Sample Clauses

Correction of Rated Continuous Current. When a line trap test temperature rise is not provided by the manufacturer, the ratings may be adjusted as follows: r I = Ir (θ /θ )1/ n Where, I = Adjusted rated continuous current corrected to the maximum temperature rise allowed for a normal rating in the event the temperature rise tested at the factory is less than the maximum allowed temperature rise. Ir = Rated continuous current (nameplate rating) that a line trap can carry continuously without exceeding its limits of observable temperature rise. This value is given by the manufacturer. θ = The Steady-state temperature-rise above ambient temperature when tested at rated continuous current (nameplate rating) in the factory.
AutoNDA by SimpleDocs
Correction of Rated Continuous Current. When a line trap test temperature rise is not provided by the manufacturer, the ratings may be adjusted as follows: r I = Ir  / 1/ n Where, I = Adjusted rated continuous current corrected to the maximum temperature rise allowed for a normal rating in the event the temperature rise tested at the factory is less than the maximum allowed temperature rise. Ir = Rated continuous current (nameplate rating) that a line trap can carry continuously without exceeding its limits of observable temperature rise. This value is given by the manufacturer.  = The Steady-state temperature-rise above ambient temperature when tested at rated continuous current (nameplate rating) in the factory.  r corresponding to I. = Limit of observable temperature rise at rated continuous current n = 1.8 ( A factor or constant) For subsequent calculations, the adjusted rated continuous current should be used when test data are available.

Related to Correction of Rated Continuous Current

  • EPP service availability Refers to the ability of the TLD EPP servers as a group, to respond to commands from the Registry accredited Registrars, who already have credentials to the servers. The response shall include appropriate data from the Registry System. An EPP command with “EPP command RTT” 5 times higher than the corresponding SLR will be considered as unanswered. If 51% or more of the EPP testing probes see the EPP service as unavailable during a given time, the EPP service will be considered unavailable.

  • Service Availability You understand that Service availability is at all times conditioned upon the corresponding operation and availability of the communication systems used in communicating your instructions and requests to the Credit Union. We will not be liable or have any responsibility of any kind for any loss or damage thereby incurred by you in the event of any failure or interruption of such communication systems or services resulting from the act or omission of any third party, or from any other cause not reasonably within the control of the Credit Union.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!