Description of Existing Facility. The Interconnection Customer has constructed a 6.4 MW landfill gas-to-energy generation facility (the “Existing Facility”) located at the Chautauqua County landfill in Xxxxxx, New York. The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxxxxx-South Dow Line #859 (“Xxxxxxxxx-South Dow Line #859”) via a single breaker tap arrangement and 4.7 mile, 34.5 kV sub-transmission line (the “Chautauqua Line”), with distribution underbuild. The Existing Facility consists of: Four (4) Caterpillar Model 3520 Engines, 1.6 MW, 2 MVa, each of which has a reactive power capability to operate from a power factor range of 0.80 lagging to 0.90 leading, giving a gross plant reactive capability of +6.6 MVAR to -4.64 MVAR at the generator terminals; One (1) three-phase 4160 (Delta)-480 /277 V (Wye), 750 kVA transformer, 60 kV BIL, 7% impedance;
Description of Existing Facility. The Interconnection Customer has constructed a 2.8 MW landfill gas generation facility located at 000 Xxxx Xxxx, Albany New York (“Existing Facility”). The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxx-Patroon Line #5 (“Xxxxxx-Patroon Line #5”) via a single breaker tap arrangement. The Existing Facility consists of: Two (2) Caterpillar Model 3516 Engine Generator Sets, 0.925 MW, 1.15 MVA, each with a power factor range of 0.80 lagging to 0.90 leading, giving a total reactive capability for both units of +1.39 MVAR to -0.896 MVAR at the generator terminals; One (1) Caterpillar Model 3516 Engine Generator Set, 0.95 MW, 1.18 MVA, with a power factor range of 0.80 lagging to 0.90 leading, giving a gross a reactive capability for the unit of +.713 MVAR to -.460 MVAR at the generator terminals; One (1) three-phase 4160 V (Delta) - 480 /277 V (Wye), 300 kVA transformer, 60 kV BIL, 6.5% impedance; One (1) ancillary circuit load breaker: 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL; Three (3) generator circuit breakers: 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL; One (1) 4.16 kV bus that will accommodate connection and protection controls; and Utility interconnection protection equipment and relaying controls. The Point of Change of Ownership (“PCO”) for the Existing Facility is on the existing riser pole (Pole 209-2) at the 34.5 kV insulators on the line side of the Interconnection Customer’s Switch 588. The Point of Interconnection (“POI”) for the Existing Facility is the tap point (Connecting Transmission Owner’s Pole 17 ½) on the Connecting Transmission Owner’s 34.5 xX Xxxxxx-Patroon Line #5 (“Line #5), xxx xxx xxxxxxxx 0 xxxx 00.0 kV Generator Lead Line.
Description of Existing Facility. The Interconnection Customer has constructed a 2.8 MW landfill gas generation facility located at 000 Xxxx Xxxx, Albany New York (“Existing Facility”). The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxx-Patroon Line #5 (“Xxxxxx-Patroon Line #5”) via a single breaker tap arrangement. The Existing Facility consists of: Two (2) Caterpillar Model 3516 Engine Generator Sets, 0.925 MW, 1.15 MVA, each with a power factor range of 0.80 lagging to 0.90 leading, giving a total reactive capability for both units of +1.39 MVAR to -0.896 MVAR at the generator terminals; One (1) Caterpillar Model 3516 Engine Generator Set, 0.95 MW, 1.18 MVA, with a power factor range of 0.80 lagging to 0.90 leading, giving a gross a reactive capability for the unit of +.713 MVAR to -.460 MVAR at the generator terminals; One (1) three-phase 4160 V (Delta) - 480 /277 V (Wye), 300 kVA transformer, 60 kV BIL, 6.5% impedance; One (1) ancillary circuit load breaker: 4.16 kV, 1200 A, 40 kAIC, 60 kV BIL;
Description of Existing Facility. As depicted in Figure 1 to Appendix A, the Existing Facility is comprised of: ● One (1) existing generator: 3-phase, 30 MW (nameplate @ 0.8 power factor)/37.5 MVA; ● One (1) turbine (Unit 1): 42,000HP, 195.9 RPM, rated for 100.8 feet of head; ● Three (3) surge capacitors–(0.50 µF); ● One (1) air circuit breaker (generator breaker R21): 15 kV, 1200 A, 25 kA; ● One (1) 13.2 kV, 1200 A, three-phase manually gang operated disconnect switch for 13.2 kV station service;
Description of Existing Facility. The Interconnection Customer owns an existing 6.4 MW landfill gas-to-energy generation facility located in Riga, New York (“Small Generating Facility”). The Small Generating Facility currently consists of eight Caterpillar 800 kW 3516 generators (“Existing Facility”). As depicted on the one-line diagram in Attachment 3, the Existing Facility includes the following equipment:
Description of Existing Facility. The Interconnection Customer has constructed a 6.4 MW landfill gas-to-energy generation facility (the “Existing Facility”) located at the Chautauqua County landfill in Xxxxxx, New York. The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxxxxx-South Dow Line #859 (“Xxxxxxxxx-South Dow Line #859”) via a single breaker tap arrangement and 4.7 mile, 34.5 kV sub-transmission line (the “Chautauqua Line”), with distribution underbuild. The Existing Facility consists of:
Description of Existing Facility. Seller and Purchaser have entered into an Accounts Receivable Purchase Agreement, dated June 27, 2003, as amended by a Modification Agreement, dated July 29, 2003, as amended by a Modification Agreement, dated May 14, 2004, as amended by a Modification Agreement, dated May 18, 2004, as amended by a Modification Agreement, dated August 2, 2004 as may be further amended from time to time. (the "Purchase Agreement"). Defined terms used but not otherwise defined herein shall have the same meanings as in the Purchase Agreement. Hereinafter, all indebtedness owing by Seller to Purchaser shall be referred to as the "Indebtedness."
Description of Existing Facility. The Interconnection Customer has constructed a 6.4 MW landfill gas-to-energy generation facility (the “Existing Facility”) located at the Chautauqua County landfill in Xxxxxx, New York. The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxxxxx-South Dow Line #859 (“Xxxxxxxxx-South Dow Line #859”) via a single breaker tap arrangement and 4.7 mile, 34.5 kV sub-transmission line (the “Chautauqua Line”), with distribution underbuild. The Existing Facility consists of: Four (4) Caterpillar Model 3520 Engines, 1.6 MW, 2 MVa, each of which has a reactive power capability to operate from a power factor range of 0.80 lagging to 0.90 leading, giving a gross plant reactive capability of +6.6 MVAR to -4.64 MVAR at the generator terminals; One (1) three-phase 4160 (Delta)-480 /277 V (Wye), 750 kVA transformer, 60 kV BIL, 7% impedance; One (1) (interconnection tie circuit breaker) 4.16kV, 2000A, 40kAIC, 60kV BIL (with 48VDC Trip and Close);
(1) (ancillary circuit load breaker) 4.16kV, 1200A, 40kAIC, 60kV BIL (with 48VDC Trip and Close); Four (4) (generator circuit breakers) 4.16kV, 1200A, 40kAIC, 60kV BIL (with 48VDC Trip and Close); One (1) 4.16 kV bus that will accommodate connection and protection controls; and Utility interconnection protection equipment and relaying controls. The Point of Change of Ownership for the Existing Facility is the line termination at the 34.5kV insulators on the Interconnection Customer’s Generator Step-up (“GSU”) Station termination structure on the line side of the load break disconnect switch. The Point of Interconnection for the Existing Facility is the tap point on the Connecting Transmission Owner’s 34.5xX Xxxxxxxxx-South Dow Line #859.
Description of Existing Facility. The Interconnection Customer has constructed a 6.4 MW landfill gas-to-energy generation facility (the “Existing Facility”) located at the Chautauqua County landfill in Xxxxxx, New York. The Existing Facility interconnects to the Connecting Transmission Owner’s 34.5 xX Xxxxxxxxx-South Dow Line #859 (“Xxxxxxxxx-South Dow Line #859”) via a single breaker tap arrangement and 4.7 mile, 34.5 kV sub-transmission line (the “Chautauqua Line”), with distribution underbuild. The Existing Facility consists of:
(1) (ancillary circuit load breaker) 4.16kV, 1200A, 40kAIC, 60kV BIL (with 48VDC Trip and Close); Four (4) (generator circuit breakers) 4.16kV, 1200A, 40kAIC, 60kV BIL (with 48VDC Trip and Close); One (1) 4.16 kV bus that will accommodate connection and protection controls; and Utility interconnection protection equipment and relaying controls.
Description of Existing Facility. As depicted in Figure 1 to Appendix A, the Existing Facility is comprised of: ● One (1) existing generator: 3-phase, 30 MW (nameplate @ 0.8 power factor)/37.5 MVA; ● One (1) turbine (Unit 1): 42,000HP, 195.9 RPM, rated for 100.8 feet of head; ● Three (3) surge capacitors–(0.50 µF); ● One (1) air circuit breaker (generator breaker R21): 15 kV, 1200 A, 25 kA; ● One (1) 13.2 kV, 1200 A, three-phase manually gang operated disconnect switch for 13.2 kV station service; ● Three (3) EJO-1, 40E fuses; ● One (1) three phase, two winding, 13.2 kV/480 V delta-delta, 300 kVA station service transformer; ● Three (3) 15 kV/12.7 kV MCOV station class surge arrestors. ● Three (3) 18 kV/15.3 kV MCOV station class surge arrestors.