Common use of Developer’s Attachment Facilities Clause in Contracts

Developer’s Attachment Facilities. Interconnection of the Large Generating Facility is achieved by means of the project substation named 9WU-BNL. The 9WU-BNL substation contains switching equipment to consolidate the field’s four (4) 13.8kV circuits, a 33MVA transformer to step the voltage to 69kV, and the required control and protection. Interconnection between 9WU- BNL and the LIPA 8ER Brookhaven Substation is achieved via a 69kV line which is direct buried and trenched approximately 3000ft. The Developer’s Attachment Facilities for the Large Generating Facility Project described in Appendix C of this Agreement are diagrammed in Figure A-1, of this Appendix A, and include:  Eight (8) 3-phase, 1200A (continuous), 25kA (interrupting), electrically operated, drawout type, vacuum 13.8kV circuit breakers including six (6) in ring bus configurations, one (1) spare, and one (1) at the switchgear output  One (1) 3-phase GOAB, 1200 A, 13.8kV switch (1) 33MVA collector transformer. Transformer is a step-up, 3-phase 13.8kV; 69kV buried ground tertiary winding, 19.8/26.4/33.0 MVA, XXXX/XXXX/XXXX, 0 xxxxx, 00 Xx, 00 Degree C rise, 67.65kV, Grd Wye to 13.8kV Wye with high voltage de-energized taps, buried grounded tertiary winding, 9% impedance at 19.8 MVA  Two (2) 3-phase GOAB, 1200A, 69kV switches  3000ft 69kV armored cable, 1-500MCM/phase  One (1) ION 8600 project meter  One (1) Shark meter for utility spare  One (1) 69kV circuit breaker, 2000A cont., 40kA int  All required protection  One (1) Control house  One (1) Battery room

Appears in 7 contracts

Samples: Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement

AutoNDA by SimpleDocs

Developer’s Attachment Facilities. Interconnection Developer will design and construct a 34.5/115 kV collector substation (“Hardscrabble Substation”) and a 115 kV bus, approximately 10 feet in length, from the Developer’s Hardscrabble Substation to the Point of Change of Ownership. Developer shall design and construct the Large Generating Facility is achieved by means of the project substation named 9WU-BNL. The 9WU-BNL substation contains switching equipment to consolidate the field’s four (4) 13.8kV circuits, a 33MVA transformer to step the voltage to 69kV, and the required control and protection. Interconnection between 9WU- BNL and the LIPA 8ER Brookhaven Substation is achieved via a 69kV line which is direct buried and trenched approximately 3000ft. The Developer’s Attachment Facilities for in accordance with the Large Generating Facility Project described applicable requirements of Transmission Owner, as set out in Appendix C National Grid Electric System Bulletin 756, dated May 2007, to the extent not inconsistent with the terms of this Agreement are diagrammed or the NYISO OATT and in Figure A-1accordance with the Transmission Owner’s project specific electrical requirements as documented in the project’s Specification for Electrical Installation dated December 4, 2007 to the extent not inconsistent with the terms of this Appendix AAgreement or the NYISO OATT. The Hardscrabble Substation shall include, and includebut is not limited to:  Eight (8) 3-phase, 1200A (continuous), 25kA (interrupting), electrically operated, drawout type, vacuum 13.8kV circuit breakers including six (6) in ring bus configurations, one (1) spare115 kV, and 1200 A, three-phase, group-operated, disconnect switch with motor operator;  one (1) at the switchgear output  One (1) 3-phase GOAB115 kV, 1200 A, 13.8kV switch 40kA SF6 circuit breaker;  three (3) 76 kV MCOV surge arresters;  one (1) 33MVA collector transformer. Transformer is a step48/64/80 MVA, wye-updelta-wye, 3-phase 13.8kV; 69kV 115/34.5 kV transformer with 13.2 kV buried ground tertiary winding;  one (1) 34.5 kV, 19.8/26.4/33.0 MVA2000 A, XXXX/XXXX/XXXXthree-phase, 0 xxxxx, 00 Xx, 00 Degree C rise, 67.65kV, Grd Wye to 13.8kV Wye with high voltage degroup-energized taps, buried grounded tertiary winding, 9% impedance at 19.8 MVA operated disconnect switch; Two twelve (212) 3-phase GOAB22 kV MCOV surge arresters;  one (1) 34.5 kV, 1200A, 69kV switches 31.5kA circuit breaker for each 34.5 kV collector circuit; 3000ft 69kV armored cable, 1-500MCM/phase  One one (1) ION 8600 project meter 34.5 kV, 1500 kVA, 600-volt buried delta secondary grounding transformer for each 34.5 kV collector circuit; and One (1) Shark meter a control enclosure for utility spare  One (1) 69kV circuit breakercontrol, 2000A contprotection, and data communication equipment., 40kA int  All required protection  One (1) Control house  One (1) Battery room

Appears in 3 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Developer’s Attachment Facilities. Interconnection of the Large Generating Facility is achieved by means of the project substation named 9WU-BNL. The 9WU-BNL substation contains switching equipment to consolidate the field’s four (4) 13.8kV circuits, a 33MVA transformer to step the voltage to 69kV, and the required control and protection. Interconnection between 9WU- BNL and the LIPA 8ER Brookhaven Substation is achieved via a 69kV line which is direct buried and trenched approximately 3000ft. The Developer’s Attachment Facilities for the Large Generating Facility Project described in Appendix C of this Agreement are diagrammed in Figure A-1, of this Appendix A, and include: Eight (8) 3-phase, 1200A (continuous), 25kA (interrupting), electrically operated, drawout type, vacuum 13.8kV circuit breakers including six (6) in ring bus configurations, one (1) spare, and one (1) at the switchgear output One (1) 3-phase GOAB, 1200 A, 13.8kV switch (1) 33MVA collector transformer. Transformer is a step-up, 3-phase 13.8kV; 69kV buried ground tertiary winding, 19.8/26.4/33.0 MVA, XXXX/XXXX/XXXX, 0 xxxxx, 00 Xx, 00 Degree C rise, 67.65kV, Grd Wye to 13.8kV Wye with high voltage de-energized taps, buried grounded tertiary winding, 9% impedance at 19.8 MVA Two (2) 3-phase GOAB, 1200A, 69kV switches 3000ft 69kV armored cable, 1-500MCM/phase One (1) ION 8600 project meter One (1) Shark meter for utility spare One (1) 69kV circuit breaker, 2000A cont., 40kA int All required protection One (1) Control house One (1) Battery room

Appears in 2 contracts

Samples: Standard Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement

Developer’s Attachment Facilities. Interconnection of the Large Generating Facility is achieved by means of the project substation named 9WU-BNL. The 9WU-BNL substation contains switching equipment to consolidate the field’s four (4) 13.8kV circuits, a 33MVA transformer to step the voltage to 69kV, and the required control and protection. Interconnection between 9WU- BNL and the LIPA 8ER Brookhaven Substation is achieved via a 69kV line which is direct buried and trenched approximately 3000ft. The Developer’s Attachment Facilities for the Large Generating Facility Project described in Appendix C of this Agreement are diagrammed in Figure A-1, of this Appendix A, and include: Eight (8) 3-phase, 1200A (continuous), 25kA (interrupting), electrically operated, drawout type, vacuum 13.8kV circuit breakers including six (6) in ring bus configurations, one (1) spare, and one (1) at the switchgear output One (1) 3-phase GOAB, 1200 A, 13.8kV switch (1) 33MVA collector transformer. Transformer is a step-up, 3-phase 13.8kV; 69kV buried ground tertiary winding, 19.8/26.4/33.0 MVA, XXXX/XXXX/XXXX, 0 xxxxx, 00 Xx, 00 Degree C rise, 67.65kV, Grd Wye to 13.8kV Wye with high voltage de-energized taps, buried grounded tertiary winding, 9% impedance at 19.8 MVA Two (2) 3-phase GOAB, 1200A, 69kV switches 3000ft 69kV armored cable, 1-500MCM/phase  One phase (1) ION 8600 project meter One (1) Shark meter for utility spare One (1) 69kV circuit breaker, 2000A cont., 40kA int All required protection One (1) Control house One (1) Battery room

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

AutoNDA by SimpleDocs

Developer’s Attachment Facilities. Interconnection of the Large Generating Facility is achieved by means of the project substation named 9WU-BNL. The 9WU-BNL substation contains switching equipment to consolidate the field’s four (4) 13.8kV circuits, a 33MVA transformer to step the voltage to 69kV, and the required control and protection. Interconnection between 9WU- BNL and the LIPA 8ER Brookhaven Substation is achieved via a 69kV line which is direct buried and trenched approximately 3000ft. The Developer’s Attachment Facilities for the Large Generating Facility Project described in Appendix C of this Agreement are diagrammed in Figure A-1, of this Appendix A, and include: Eight (8) 3-phase, 1200A (continuous), 25kA (interrupting), electrically operated, drawout type, vacuum 13.8kV circuit breakers including six (6) in ring bus configurations, one (1) spare, and one (1) at the switchgear output One (1) 3-phase GOAB, 1200 A, 13.8kV switch (1) 33MVA collector transformer. Transformer is a step-up, 3-phase 13.8kV; 69kV buried ground tertiary winding, 19.8/26.4/33.0 MVA, XXXXONAN/XXXXONAF/XXXXONAF, 0 xxxxx3 phase, 00 Xx60 Hz, 00 65 Degree C rise, 67.65kV, Grd Wye to 13.8kV Wye with high voltage de-energized taps, buried grounded tertiary winding, 9% impedance at 19.8 MVA Two (2) 3-phase GOAB, 1200A, 69kV switches 3000ft 69kV armored cable, 1-500MCM/phase  One phase (1) ION 8600 project meter One (1) Shark meter for utility spare One (1) 69kV circuit breaker, 2000A cont., 40kA int All required protection One (1) Control house One (1) Battery room

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement