Common use of Developer’s Attachment Facilities Clause in Contracts

Developer’s Attachment Facilities. i) General Description: Developer’s Attachment Facilities consist of three (3) 18/355kV Generator Step-Up transformers (“GSU”) that feed from each GSU primary side underground Nexans type, XLPE Solid Dielectric Cable feeders to a collecting ABB type Gas Insulated Switchgear (“GIS”). The GIS has one set of motor operated disconnect switches and motor operated grounding switches for each incoming GSU feeder cable. The GIS has one main outlet feeder (“G13”), which also contains one set of motor operated disconnect switches and motor operated grounding switches. G13 is one three (3) phase feeder, made up of parallel 1,192kcmil Xxxxxxx aerial cable, with a total circuit length of 2,000 feet.

Appears in 11 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement