Common use of Disconnect Device Clause in Contracts

Disconnect Device. A safety manual disconnect switch of the visible load break type shall be installed by the customer. The disconnect switch shall be visible to and readily accessible by Utility personnel. The switch shall be capable of being locked in the open position and shall prevent the generator from supplying power to the distribution system.

Appears in 4 contracts

Samples: Customer Owned Generating Facilities Interconnection Agreement, Customer Owned Generating Facilities Interconnection Agreement, Interconnection Agreement

AutoNDA by SimpleDocs

Disconnect Device. A safety manual disconnect switch of the visible load break type shall be installed by the customer. The disconnect switch shall be visible to and readily accessible by Utility SCMEU and St. Xxxxxxx Emergency and Fire Department personnel. The switch shall be capable of being locked in the open position and shall prevent the generator from supplying power to the distribution system.

Appears in 1 contract

Samples: Customer Owned Generating Facilities Interconnection Agreement

Disconnect Device. A safety manual disconnect switch of the visible load break type shall be installed by the customer. The disconnect switch shall be mounted within two feet of electrical meter and visible to and readily accessible by Utility City personnel. The switch shall be capable of being locked in the open position and shall prevent the generator from supplying power to the distribution system.

Appears in 1 contract

Samples: Customer Owned Generating Facilities Interconnection Agreement

Disconnect Device. A safety manual disconnect switch of the visible load break type shall be installed by the customer. The disconnect switch shall be visible to and readily accessible by Utility XXXXX and St. Xxxxxxx Emergency and Fire Department personnel. The switch shall be capable of being locked in the open position and shall prevent the generator from supplying power to the distribution system.

Appears in 1 contract

Samples: Customer Owned Generating Facilities Interconnection Agreement

AutoNDA by SimpleDocs

Disconnect Device. A safety manual disconnect switch of the visible load break type shall be installed by the customer. The disconnect switch shall be visible to and readily accessible by Utility personnel. The switch shall be capable of being locked in the open position and shall prevent the renewable generator from supplying power to the distribution system.

Appears in 1 contract

Samples: Interconnection Agreement