Electrical testing Sample Clauses
Electrical testing. To test all circuits for shorts and earthing and to balance loads on all panels.
Electrical testing. To test all circuits for shorts and earthing and to balance loads on all panels. Passage of wires pipes cables etc The Tenant agrees that permanent utility lines may pass through the ceiling cavity of the Premises to service other premises and areas in the Building. Emergency lighting To provide battery operated type emergency lighting and exit signs in locations within the Premises as required by any codes and regulations, and as deemed necessary by the Landlord. 18
Electrical testing. 6.5.1 All temporary electrical installations set up be the Company on sites will conform to the following Codes of Practice under the Occupational Health and Safety Act and regulations (“OH&S Act”) (as amended from time to time); • Electrical Practices for Construction Work • Low Voltage Electrical Work
6.5.2 All flexible extension cords, portable tools and electrical plant used on voltages above 32 volts will be inspected tested and tagged monthly by a licensed electrician in accordance with details set out in the Codes of Practice. All extension cords, portable tools, electrical plant brought on to the site by the Company will bear the correct monthly tag. The Company will keep a log book of all inspections of the equipment. The Principal’s representative shall be able to inspect these log books on a random basis to ensure that safety requirements are being adhered to. Any equipment found without a valid inspection tag will be disconnected and removed from the site until the equipment has been re-inspected and a new inspection tag attached. All temporary electrical work and installations must confirm to the OH&S Act, and the Electrical Safety Act 1995 (as amended from time to time). All welding units shall be fitted with either a voltage reduction device (VRD) in accordance with the provisions of AS 1674 or a trigger switch that opens the welding circuit unless it is closed complying with AS 1674.
Electrical testing. FIXED INSTALLATIONS 5.1. Provision of a fixed electrical installation test in accordance with current IEE Recommendations every five years.
Electrical testing. Electrical testing and Certification to current IEE regulations Per single column …Included in contract….
Electrical testing. Prior to completion of the work, the Contractor shall cause the following tests to be made on any or all new electrical circuits, as required by the Engineer and in the presence of the Maintaining Agency representative:
1. Test for continuity of each circuit.
2. A visual inspection of all grounding connections. Electrical equipment and components shall not be energized unless properly grounded as specified in the Contract Documents and directed by the Engineer.
3. A megohmeter test on each single conductor circuit between the circuit conductor and all other circuits and ground as specified in the Contract Documents and directed by the Engineer.
a. The insulation resistance shall not be less than 500 megohms when tested at 500 volts.
b. Individual conductors in traffic signal cable, RF cable, Opticom cable, CCTV power cable, communications cable, other multi-conductor cables, and coaxial cables shall be exempted from the megohm testing by the Engineer if a visual inspection of these cables shows no suspicious cuts, tears, or other damage to the outside insulation.
c. Under no circumstances shall street light fixtures, video detection cameras, or other low voltage components be subjected to the high voltage of this test.
4. A flash test for traffic signal installations to verify the terminals and connections before turn-on.
5. A functional test in which it is demonstrated that all parts of the system function as specified or intended.
6. Any fault in any material or in any part of the installation revealed by these tests shall be replaced or repaired by the Contractor immediately. All repairs and material replacements shall be completed to the satisfaction of the Engineer.
Electrical testing. Electrical health check of pumps/motors etc via megga meter phase-to-earth and phase-to-phase. This is to build trends to determine any deterioration in electrical insulation • Amps drawn via clamp meter to compare with manufacturers recommendations and electricity trip rating • Voltage/current trace through components • All panel components for integrity, duty assist/changeover operation • Alarm tests when applicable for: - Pump Trip - Hi-Level - Loss of Pressure - Loss of Rotation - Loss of Power Mechanical Testing... • Mechanical test of following items when applicable: - Pumps for blockages, defects, oil leaks etc - Hanging chains for corrosion - Floats for current depth, operating stroke - Pipework for splits, corrosion - Check valve for correct operation - Drive trains for alignment - Guide rails • Bacterial processes for correct growth (Sewage Treatment Plant) • Physical test of lid, frame and surrounding area • Visual inspection of the whole system for defects • Any causes for concern put forward to customer • Detailed service report provided • Desludge Management (This helps to maximise efficiency of plant & keep within discharge consent levels) • Sampling (Effluent quality samples via accredited laboratories)
