Room Temperature Clause Samples

The Room Temperature clause sets out the required temperature range that must be maintained within a specified space, such as an office, apartment, or commercial premises. Typically, it details acceptable minimum and maximum temperatures, and may assign responsibility for monitoring and adjusting heating or cooling systems to the landlord or tenant. This clause ensures occupant comfort and prevents disputes by clearly defining environmental expectations and maintenance obligations.
POPULAR SAMPLE Copied 1 times
Room Temperature. Uncomfortable working areas limit the effectiveness of teaching and learning. Neither students nor bargaining unit members should be required to work prolonged periods of time in an environment that is physically, unreasonably uncomfortable. When such conditions exist, the bargaining unit member shall report the temperature of the room or area to the building principal. Adjustments or changes will be made to remedy or modify the temperature by the building custodial staff or district maintenance personnel within a reasonable length of time. If the condition cannot be corrected within a reasonable length of time, the bargaining unit member may request that the building principal attempt to relocate the class in a more favorable environment.
Room Temperature. Resident is responsible for keeping the room temperature above 55 degrees at all times. The AC can be set no lower than 70 degrees Fahrenheit.
Room Temperature. Resident is responsible to keep the room temperature above 55 degrees at all times.
Room Temperature. 1. The room temperature is measured at six specified reference measuring points on the upper floors of the following buildings on TU Dortmund University’s campus: • ▇▇▇▇-▇▇▇▇▇-Str. 50, 44227 Dortmund • ▇▇▇▇▇▇▇▇▇▇▇▇▇ ▇▇, ▇▇▇▇▇ ▇▇▇▇▇▇▇▇ • ▇▇▇▇-▇▇▇▇▇-Str. 66, 44227 Dortmund • ▇▇▇▇-▇▇▇▇-Str. 6, 44227 Dortmund • ▇▇▇▇-▇▇▇▇▇-Str. 61, 44227 Dortmund • ▇▇▇▇▇▇-▇▇▇▇▇▇▇-Str. 8, 44227 Dortmund The aforementioned reference measuring points are located in rooms that experience has shown to heat up strongly during summer temperatures (worst-case measuring points). They can be changed for factual reasons. 2. The values measured between 11:00 - 14:00 h are collected, evaluated and averaged by the Central Control Center of the university and then forwarded to the Office of Occupational Safety, Environmental and Health Protection. If the room temperature measured at the reference measuring points reaches more than 26°C at more than three of the six measuring points, it is to be assumed that there is exposure to heat. The Office of Occupational Safety, Environmental and Health Protection, with the involvement of the Office of University Communications, conveys that there is a heat load within the meaning of this service agreement. This is done, for example, by means of a traffic light system on the university homepage and an e-mail to all employees. 3. If the room temperature of 35°C is exceeded and proven by room-specific measurement, the room is not suitable as a workroom for the time the temperature is exceeded. A suitable alternative solution with regard to the work location must be found in consultation with the supervisors.

Related to Room Temperature

  • Temperature Where low temperature and/or self-service cases are used for any of such merchandise coming under the jurisdiction of the Union, such cases shall be served only by employees covered by this Agreement.

  • Calibration The comparison of a measurement system or device of unverified accuracy with a measurement system of known and greater accuracy to detect deviation of the unverified measurement system from required performance specifications (of the unverified measurement system or device) and to quantify all measured values to applicable units of the international system of units.

  • Meters 7.1.1 For installation of Meters, Meter testing, Meter calibration and Meter reading and all matters incidental thereto, the SPD and SECI shall follow and be bound by the Central Electricity Authority (Installation and Operation of Meters) Regulations, 2006, the Grid Code, as amended and revised from time to time. 7.1.2 The SPD shall bear all costs pertaining to installation, testing, calibration, maintenance, renewal and repair of meters at SPD’s side of Delivery Point. 7.1.3 In addition to ensuring compliance of the applicable codes, the SPD shall install Main & Check meters at the Delivery Point, along with Stand-by meter(s) as per the applicable Central/State regulations. 7.1.4 In case of pooling of multiple Projects, power from multiple Projects can be pooled at a Pooling Substation prior to the Delivery point and the combined power can be fed at Delivery point through a common transmission line from the Pooling Substation. In such cases, ABT compliant sub-meters as per relevant regulation/approval are also to be set up at pooling substation for individual projects in addition to the meters at Delivery Point as described in clause 7.1.3.

  • Ventilation Where noxious or poisonous gases may accumulate, the City shall provide proper protection and ventilation. Proper lighting and ventilation shall be provided for all enclosed working spaces. All work in enclosed and confined spaces shall be performed in accordance with applicable Federal, State and local regulations. Spray painting shall be done only by qualified painters.

  • Configuration The configuration for the Purchase Right Aircraft will be the Detail Specification for Model 767-3S2F aircraft at the revision level in effect at the time of the Supplemental Agreement. Such Detail Specification will be revised to include (i) changes required to obtain required regulatory certificates and (ii) other changes as mutually agreed upon by Boeing and Customer.