Security Fence and Security System Clause Samples

Security Fence and Security System. The entire perimeter of the Site shall be enclosed by an appropriately designed security fence at least 2.2m in height and built according to best trade practice to a strength and security suitable for the facility protected. The fence shall enclose all Hazardous Areas. Note that a temporary fence is also required during construction to isolate the working area from the rest of the Owner's facility. Personnel access gates shall be provided at no less than three locations around the perimeter fence, each fitted with automatic entry control using Cardax card swipes and "breakglass" emergency opening. The Cardax system shall be connected to and fully integrated with the Wairakei Station Cardax system and shall automatically release in the event of a fire alarm in the Binary Plant area. One vehicle access gate shall also be automated. Other vehicle access gates may be manually operated and locked. The Contractor shall submit details of the permanent security fence design to the Owner for approval prior to construction.