Common use of Undervoltage Ride-Through Clause in Contracts

Undervoltage Ride-Through. The Facility, as a whole, will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the Point of Interconnection). [THESE VALUES MAY BE CHANGED BY COMPANY UPON COMPLETION OF THE IRS. WITHOUT LIMITATION, FOR A DISTRIBUTION-CONNECTED FACILITY, UPON COMPLETION OF THE IRS THE COMPANY MAY SPECIFY REQUIREMENTS FOR A MANDATORY DISCONNECTION FROM THE COMPANY SYSTEM.]: 0.88 pu  V  1.00 pu The Facility remains connected to the Company System. 0.70 pu  V < 0.88 pu The Facility may initiate disconnection from the Company System if the voltage remains in this range for more than 20 seconds.

Appears in 10 contracts

Samples: Power Purchase Agreement, Power Purchase Agreement, Scheduled and Contingency Capacity Purchase Agreement

AutoNDA by SimpleDocs

Undervoltage Ride-Through. The Facility, as a whole, will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the Point of Interconnection). [THESE VALUES MAY BE CHANGED BY COMPANY UPON COMPLETION OF THE IRS. WITHOUT LIMITATION, FOR A DISTRIBUTION-CONNECTED FACILITY, UPON COMPLETION OF THE IRS THE COMPANY MAY SPECIFY REQUIREMENTS FOR A MANDATORY DISCONNECTION FROM THE COMPANY SYSTEM.]: 0.88 pu  V  1.00 pu The Facility remains connected to the Company System. 0.70 pu  V < 0.88 pu The Facility may initiate disconnection from the Company System if the voltage remains in this range for more than 20 seconds.

Appears in 3 contracts

Samples: Energy Storage Power Purchase Agreement, Energy Storage Power Purchase Agreement, Energy Storage Power Purchase Agreement

AutoNDA by SimpleDocs

Undervoltage Ride-Through. The Facility, Facility (as a whole, ) will meet the following undervoltage ride-through requirements during low voltage affecting one or more of the three voltage phases ("V" is the voltage of any three voltage phases at the Point point of Interconnectioninterconnection). [THESE VALUES MAY BE CHANGED BY THE COMPANY UPON COMPLETION OF THE IRS. WITHOUT LIMITATION, FOR A DISTRIBUTION-CONNECTED FACILITY, UPON COMPLETION OF THE IRS THE COMPANY MAY SPECIFY REQUIREMENTS FOR A MANDATORY DISCONNECTION FROM THE COMPANY SYSTEM.]: 0.88 pu  V  1.00  0.80 pu The Facility remains connected to the Company System. 0.70 0.75 pu  V < 0.88 ≤ 0.80 pu The Facility may initiate disconnection from the Company System if the voltage remains in this range for more than 20 2 seconds. 0.00 pu  V ≤ 0.75 pu The Facility may initiate disconnection from the Company System if voltage remains in this range for more than 600 milliseconds.

Appears in 1 contract

Samples: 3 Power Purchase Agreement