UPS. This section will only appear when Power Panel Business Edition software is linked with a UPS that supports cumulative energy in the LCD screen. Cumulative Energy: Present the cumulative energy data stored in the UPS. Energy Settings In this page, we can set the average rate of power consumption and carbon emission by selecting the country, or assign and apply a customized rate. When rates are updated, the information displayed in the energy reporting page will also be updated.
UPS. United Property Systems, LLC, a Delaware limited liability company and a wholly-owned Subsidiary of CMGI, and its successors and assigns. Willbridge Terminal Facility. The fee, leasehold, easement, right-of-way and/or other real property interests, together with all improvements thereon owned by LCP Oregon Holdings, LLC, a wholly-owned Subsidiary of Borrower, with respect to the Willbridge petroleum products terminal facility located in Portland, Oregon. Willbridge Terminal Facility Lease. That certain Lease dated January 28, 2014 between Arc Terminals Holdings LLC, as Lessee, and LCP Oregon Holdings, LLC, as Lessor, covering the Willbridge Terminal Facility.
UPS. 1) The contractor has to keep the UPS dust free.
2) Contractor has to check and ensure proper earth.
3) Contractor has to check the load of UPS along with computer peripherals. If it is beyond the capacity disconnect the peripherals like printers etc. And connect them with other power source.
4) If Battery is not working, it shall be replaced with new one provided by BHEL, in consultation with BHEL Representative. All other items like UPS Boards, other hardware are in contractor scope.
UPS. The UPS tab allows you to set up to connect the PDU with the monitored UPS in the Center. Select the Connect to UPS option. Enter UPS IP address and assign the connected outlet. Click OK button to initiate a negotiation to connect PDU with a UPS. When the PDU connects to the UPS successfully, this PDU connects to the assigned outlet. All Clients which have communicated with this PDU will also establish the communication with UPS. The UPS tab also allows you to set to connect the ATS with the UPS in Center. Select the Source A connect to UPS (or Source B connect to UPS) option. Enter UPS IP address and assign the connected outlet for according input source of ATS. Click OK button to initiate a negotiation to connect ATS with the UPS. When ATS connects to the UPS successfully, all Clients which have communicated with ATS will also establish the communication with UPS. Do not connect both sources to one single UPS. An ATS whose sources come from the same UPS cannot protect connected computers and equipment from the power outage. When one or more Clients are detected not to establish the communication with the UPS, the Center will show a warning to inform users of this condition.
UPS. The Provider must include necessary Uninterruptible Power Supply (UPS) capacity to those parts of the solution where a power loss could cause data loss or corruption, instability or other long-term negative effects on the solution. The solution should be able to be fully-enabled upon restoration of power without reconfiguration or significant intervention. Therefore necessary included servers and DocuSign Envelope ID: 22B4BD01-58D9-4AB3-AC4F-AC67D3B96B81 DocuSign Envelope ID: 16287D28-3264-44F2-80BB-D4454384C31A DocuSign Envelope ID: 4CCD5CFA-F6B1-45E1-BC0F-C2E6C9AD484C DocuSign Envelope ID: B0369851-91DB-4C5C-AB37-4DDE5FED74CC key infrastructure devices such as switches and wireless access points shall have a UPS with capacity to allow for those devices to remain operative in the case of a power outage as necessary. This UPS should allow personnel or automated systems enough time to adequately shut down the server(s) or the infrastructure devices to avoid data loss or corruption.
UPS. 5.3.21.1 All UPS’s shall come with an embedded Modbus TCP interface ports.
5.3.21.1.1 The Contractor shall use an RS 485 cable as an interface link between the UPS and an Ethernet I/O gateway.
5.3.21.1.2 The Contractor shall also refer to the typical drawings listed in section 2.1.1 of the tender document.
UPS. The UPS system shall provide low voltage AC power to vital circuits that require uninterruptible AC power and are considered vital for the safe operation and monitoring of the equipment during both normal and transient operating conditions. Typical loads that are considered for connection to the UPS include the distribution control system, the turbine supervisory instrumentation, programmable logic controllers (PLCs), shutdown networks, and certain vendor-supplied control panels. The UPS system shall provide continuous 120 volt, 60 Hz power to the vital systems at the Facility. During normal operation, the station DC system shall provide power to the UPS inverter. The inverter shall convert the DC to 120 volt AC and provide power to the distribution panel through a static switch. A backup feed from the alternate AC power source shall power the step-down transformer. The output of the transformer shall be the second power source connected to the static switch. The static transfer switch shall automatically transfer to the alternate AC source when output voltage of the inverter deteriorates. Upon loss of synchronization, the static switch shall inhibit transfer to the alternate AC power source. A manual bypass switch shall provide a means to remove the inverter, battery, and static switch from service without interrupting the power to the distribution panel. The UPS system shall consist of the following components. Static inverter Static transfer switch Alternate source transformer Manual make-before-break bypass switch Two AC circuit breakers (alternate input and bypass source) One DC circuit breaker with shunt trip Vital 120 V AC distribution panel with fused disconnects or breakers Controls, indicating lights, meters and alarm to control the UPS
UPS. An Uninterrupted Power Supply (UPS) shall be provided for each rack by the government. One UPS will be required to be hard wired to existing disconnect. Contractor shall provide length of pigtail required to reach the disconnect.The other UPS shall be connected to existing L630R outlet. Contractor shall provide pigtail/extension to reach outlet.
UPS. JTC shall provide an uninterrupted power source to back up the AC circuit referenced in Section 6.1.
UPS. Tenant shall have the right to install an uninterrupted power system in the Premises (the “UPS”), subject to the prior approval of Landlord as to the specifications, the location of the UPS within the Premises and the manner in which the UPS will be installed, provided that Landlord shall provide approval or reasons for disapproval with respect to such matters within 10 days following Tenant’s submittal of the plans and specifications for the UPS. Tenant shall be responsible for the cost of all electricity consumed in connection with the operation of such UPS and, at Landlord’s option if Tenant is no longer the Sole Tenant of the Building, for the cost of installing a submeter to measure such electrical consumption. Tenant shall be solely responsible for the maintenance and repair of the UPS. Upon installation, the UPS shall constitute a Leasehold Improvement and, at Landlord’s option, a Required Removable pursuant to Section 8 of the Lease.