Common use of Disconnect Switch Clause in Contracts

Disconnect Switch. The Cooperative may require the interconnection Customer to install a manual load- break disconnect switch or safety switch as a clear visible indication of switch position between the Cooperative System and the interconnection Customer. The switch must have padlock provisions for locking in the open position. The switch must be visible to, and accessible to Cooperative personnel. The switch must be in close proximity to, and on the Interconnection Customer's side of the point of electrical interconnection with the Cooperative's system. The switch must be labeled "

Appears in 3 contracts

Samples: www.sremc.com, www.aemc.coop, www.aemc.coop

AutoNDA by SimpleDocs

Disconnect Switch. The Cooperative may require the interconnection Interconnection Customer to must install a manual load- break disconnect switch or safety switch as a clear visible indication of switch position between the Cooperative System and the interconnection Interconnection Customer. The switch must have padlock provisions for locking in the open position. The switch must be visible to, and accessible to Cooperative personnel. The switch must be in close proximity to, and on the Interconnection Customer's side of the point of electrical interconnection with the Cooperative's system. The switch must be labeled "

Appears in 1 contract

Samples: www.aemc.coop

AutoNDA by SimpleDocs
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!