Interconnected Transmission Owner None. 4.0 Subject to modification pursuant to the Negotiated Contract Option and/or the Option to Build under the Interconnection Construction Service Agreement, Interconnection Customer shall be subject to the estimated charges detailed below, which shall be billed and paid in accordance with Appendix 2, Section 11 of this ISA and the applicable Interconnection Construction Service Agreement.
Interconnected Transmission Owner None. Attachment Facilities ▪ Three (3) 230kV, 3000 amp, 50kA SF6 circuit breakers ▪ Three (3) 230kV, 3000 amp center-break disconnect switches. ▪ One (1) 230kV, 2000 amp, 40kA SF6 circuit breakers ▪ One (1) 230kV, 2000 amp center-break disconnect switches. ▪ Five (5) 230kV, Relay Accuracy CCVT’s. ▪ 5” aluminum bus, steel support structures (including switch supports, bus supports, CCVT supports and arrester supports), conduit, control cable and cable trough, grounding material, conductor and connectors, and foundations as required. Direct Connection Network Upgrades
Interconnected Transmission Owner None. The Interconnected Transmission Owner shall construct and, unless otherwise indicated, shall own the following Transmission Owner Interconnection Facilities: