Common use of Retaining Walls and Miscellaneous Structures Clause in Contracts

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 13 contracts

Samples: Contract for Engineering Services, Contract for Engineering Services, Contract for Engineering Services

AutoNDA by SimpleDocs

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 4 contracts

Samples: Contract for Engineering Services, Contract for Engineering Services, Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical ManualManual and project geotechnical report, if provided. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls typewall types, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must shall include: o : 1. Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet SF to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State. 2. Mechanically Stabilized Earth (MSE) Walls. The Engineer shall prepare the retaining wall layouts showing plan and profile or retaining walls for design by a State approved vendor. The Engineer is responsible for design of geometry and wall stability. The Engineer shall incorporate a slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall. 3. Concrete Block Walls (Structural and Landscape). 4. Tied Back Walls.

Appears in 2 contracts

Samples: Contract for Engineering Services, Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals the Geotechnical Manual and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and or Fill locationlocations. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as an option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 2 contracts

Samples: Contract for Engineering Services, Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. If weak foundation soils are discovered that require remediation or treatment, additional geotechnical evaluation and design services will be provided as needed, at the written request of the State’s Project Manager. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCPTraffic Control Plan. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. DocuSign Envelope ID: 639E691C-A3CC-4853-AD7B-C269303B6046 The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: DocuSign Envelope ID: 26034EA5-ACB8-461C-95D3-B7AB2C670BD8 Legacy Contract No. 12-6IDP5054 PeopleSoft Contract No. 4952 o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavementwalls, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must shall include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet SF to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the TxDOT Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls typewall types, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) ), and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the StateFBCTRA early in the plan preparation process. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, reconstruction and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technologythat have retaining walls, the Engineer shall develop the retaining walls shall be represented wall layouts in the 3D corridor model. The approximate limits of each retaining wall shall must be based on Station station or length. The Engineer shall notify the State FBGPTRA of the type of retaining walls that will be used for each cut and Cut and Fill fill location. Retaining wall types considered by the Engineer must include: o Spread Footing Walls • Mechanically Stabilized Earth (High Footing Pressure Design and Low Footing Pressure Design)MSE) Walls. The Engineer shall select prepare the retaining wall layouts showing plan and profile or retaining walls for design by a spread footing TxDOT approved vendor. The Engineer is responsible for design of geometry and wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stemstability. The Engineer shall notify incorporate a slope of 4:1 or flatter from the State when existing and finished ground line elevation to the face of the retaining wall. The Engineer shall provide layouts (scale 1” =100’), elevations, quantity is less than 1000 square feet to have estimate, summary of quantities, typical cross sections, and structural details of all retaining walls within the project. If available, approximate lengths of the retaining walls as option shown on the schematic will be specified in the plans to cast in place a spread footing wall designwork authorization. This selection has to be approved to StateThe Engineer shall determine if any additional walls are required and verify the need for and length of the retaining walls as shown on the schematic. If applicable, FBCTRA will provide architectural standard drawings for the retaining walls. The Engineer shall incorporate architectural standard drawings into the design details.

Appears in 1 contract

Samples: Engineering Services Agreement

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. DocuSign Envelope ID: 8B0EE02C-E455-423C-9476-3FA4EBD98809 For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.. • Mechanically Stabilized Earth (MSE) Walls. The Engineer shall prepare the retaining wall layouts showing plan and profile or retaining walls for design by a State approved vendor. The Engineer is responsible for design of geometry and wall stability. The Engineer shall incorporate a slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall. • Concrete Block Walls (Structural and Landscape). • Tied Back Walls. • Soil Nailed Walls. • Rock Nailed Walls. • Drilled Shaft Walls. • Temporary MSE Walls. The Engineer shall provide layouts (scale 1”=100’), elevations, quantity estimate, summary of quantities, typical cross sections and structural details of all retaining walls within the project. Approximate lengths of the retaining walls as shown on the schematic are listed as below. The Engineer shall determine if any additional walls are required and verify the need for and length of the retaining walls as shown on the schematic. If applicable, the State will provide architectural standard drawings. The Engineer shall incorporate architectural standard drawings into design details. The specific requirements for each item are as follows:

Appears in 1 contract

Samples: Contract for Engineering Services Supplemental Agreement No. 1

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the current edition of TxDOT’s Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and construction determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut cut and Fill fill location. Retaining wall types must include: o Spread Footing Walls  Mechanically Stabilized Earth (High Footing Pressure Design and Low Footing Pressure Design)MSE) Walls. The Engineer shall select prepare the retaining wall layouts showing plan and profile or retaining walls for design by a spread footing State approved vendor. The Engineer is responsible for design of geometry and wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stemstability. The Engineer shall notify incorporate a slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall.  Temporary MSE Walls. The Engineer shall provide layouts (scale 1”=100’), elevations, quantity estimate, summary of quantities, typical cross sections and structural details of all retaining walls within the project. Approximate lengths of the retaining walls as shown on the schematic are listed as below. The Engineer shall determine if any additional walls are required and verify the need for and length of the retaining walls as shown on the schematic. If applicable, the State when the quantity is less than 1000 square feet to have will provide architectural standard drawings. The Engineer shall incorporate architectural standard drawings into design details. The specific requirements for each item are as option in the plans to cast in place a spread footing wall designfollows: 1. This selection has to be approved to State.Layout Plan

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Agreement for Plan, Specification, and Estimate Design Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of DocuSign Envelope ID: 5174409E-E49B-4D11-8837-551F1909917A retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of DocuSign Envelope ID: FD24F92F-6139-4C7F-AA82-1622E42AE476 retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o : 1. Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State. 2. Mechanically Stabilized Earth (MSE) Walls. The Engineer shall prepare the retaining wall layouts showing plan and profile or retaining walls for design by a State approved vendor. The Engineer is responsible for design of geometry and wall stability. The Engineer shall incorporate a slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall. 3. Concrete Block Walls (Structural and Landscape). 4. Tied Back Walls. 5. Soil Nailed Walls. 6. Rock Nailed Walls.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall design for thirty-two (32) retaining walls located within the project limits. The Engineer shall design for additional locations (including noise walls) within the projects limits, as needed, at the written request of the State’s Project Manager to be considered as supplemental agreement. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. If weak foundation soils are discovered that require remediation or treatment, additional geotechnical evaluation and design services will be provided as needed, at the written request of the State’s Project Manager, to be considered as a supplemental agreement. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: DocuSign Envelope ID: 00030A7D-3D10-434B-B077-86515E98EAAF o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must shall include: o : 1. Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet SF to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State. 2. Mechanically Stabilized Earth (MSE) Walls. The Engineer shall prepare the retaining wall layouts showing plan and profile or retaining walls for design by a State approved vendor. The Engineer is responsible for design of geometry and wall stability. The Engineer shall incorporate a slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall. 3. Concrete Block Walls (Structural and Landscape). 4. Tied Back Walls.

Appears in 1 contract

Samples: Supplemental Agreement

AutoNDA by SimpleDocs

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o : 1. Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State. 2. Mechanically Stabilized Earth (MSE) Walls. The Engineer shall prepare the retaining wall layouts showing plan and profile or retaining walls for design by a State approved vendor. The Engineer is responsible for design of geometry and wall stability. The Engineer shall incorporate a DocuSign Envelope ID: 81F7252A-C4FA-4500-8C54-29C866EB3486 slope of 4:1 or flatter from the existing and finished ground line elevation to the face of the retaining wall. 3. Concrete Block Walls (Structural and Landscape).

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of DocuSign Envelope ID: 487DF4F5-443A-402D-88BD-EC5BD0BE2A0F retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical ManualManual and project geotechnical report, if provided. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls typewall types, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technologythat have retaining walls, the Engineer shall develop the retaining walls shall be represented wall layouts in the 3D corridor model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must shall include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet SF to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when DocuSign Envelope ID: DE976FF4-2D56-4B5B-B430-D8ABBAC3EC05 considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. DocuSign Envelope ID: F9AD1D3C-C2EE-4E82-9C7E-21604456077D The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. DocuSign Envelope ID: 981599F8-5D6E-41E6-ADFA-1DA0DC55F35E The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals the Geotechnical Manual and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining DocuSign Envelope ID: F4888AB1-5DA1-49AB-A751-51413985E885 walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and or Fill locationlocations. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as an option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of DocuSign Envelope ID: EE409C2E-41D7-48B7-8169-C48996185D1B retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. DocuSign Envelope ID: F04D8EFA-7DC2-4EDC-AAF6-887BB1F875D0 The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. DocuSign Envelope ID: CB7B82B2-FA3B-4DDD-957A-C5AE0E5F436A The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Retaining Walls and Miscellaneous Structures. The Engineer shall develop each retaining wall design and determine the location of each soil boring needed for the foundation design of each retaining wall in accordance with the Geotechnical Manual. Prior to preparation of retaining wall layouts, the Engineer shall prepare a comparative cost analysis of different types of retaining walls versus roadway embankment, pavement, soil stabilization, retaining walls type, and available ROW to determine optimum selection based on economics, construction time duration, ROW encroachments (need for construction easements) and construction feasibility. The Engineer shall submit early in the plan preparation the retaining wall layouts to obtain approval from the State. The Engineer shall incorporate all necessary information from above referenced manuals and respective checklists into the retaining wall layouts. For stage construction, the Engineer shall indicate limits of existing retaining walls for removal and reconstruction, and determine limits of temporary retaining walls to be shown on the TCP. For projects designed using Bentley’s OpenRoads 3D modelling Technology, the retaining walls shall be represented in the 3D model. DocuSign Envelope ID: 8F4C5F80-CEA4-4B7A-AA13-EF50310E0F8C The approximate limits of each retaining wall shall be based on Station or length. The Engineer shall notify the State the type of retaining walls that will be used for and Cut and Fill location. Retaining wall types must include: o Spread Footing Walls (High Footing Pressure Design and Low Footing Pressure Design). The Engineer shall select a spread footing wall for fill situation when considerable room behind the walls is available for forming, constructing, and backfilling the footings and stem. The Engineer shall notify the State when the quantity is less than 1000 square feet to have as option in the plans to cast in place a spread footing wall design. This selection has to be approved to State.

Appears in 1 contract

Samples: Contract for Engineering Services

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!