Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 13 contracts
Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 12 contracts
Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 12 contracts
Samples: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Transformer. The 11546-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 7 contracts
Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Service Agreement
Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2556
Appears in 6 contracts
Samples: Interconnection Agreement, Service Agreement, Service Agreement
Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then SERVICE AGREEMENT NO. 2550 both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 4 contracts
Samples: Standard Small Generator Interconnection Agreement, Service Agreement, Interconnection Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, SERVICE AGREEMENT NO. 2571 then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 4 contracts
Samples: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Transformer. The 115-34.5kV 115/34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 3 contracts
Samples: Interconnection Agreement, Service Agreement, Interconnection Agreement
Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, SERVICE AGREEMENT NO. 2573 then both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 3 contracts
Samples: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2554
Appears in 3 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Transformer. The 115-34.5kV 115–34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 2 contracts
Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Transformer. The 115-34.5kV 115–34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 2 contracts
Samples: Interconnection Agreement, Standard Small Generator Interconnection Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2555
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Transformer. The 115-34.5kV 34.5 kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2576
Appears in 2 contracts
Samples: Interconnection Agreement, Interconnection Agreement
Transformer. The 11569-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both SERVICE AGREEMENT NO. 2662 phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will All microprocessor differential relays shall have phase and ground time and instantaneous SERVICE AGREEMENT NO. 2647 overcurrent protection enabled. Transformer relay protection shall operate separate lockout relays to trip and block the necessary breakers.through a lockout
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Transformer. The 115230-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both differential relays with backup phase and ground time and instantaneous protection shall be providedovercurrent protection. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 1 contract
Samples: Interconnection Agreement
Transformer. The 11569-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.
Appears in 1 contract
Samples: Service Agreement
Transformer. The 115-34.5kV 34.5 kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 1 contract
Samples: Interconnection Agreement
Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous Transformer relay protection shall be providedoperate through a lockout (86) relay. Each of the two schemes will transformer protective relay shall operate separate its own dedicated lockout relays to trip and block the necessary breakersrelay.
Appears in 1 contract
Samples: Service Agreement
Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then SERVICE AGREEMENT NO. 2574 both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.
Appears in 1 contract