Common use of Transformer Clause in Contracts

Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 13 contracts

Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement

AutoNDA by SimpleDocs

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 12 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 12 contracts

Samples: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Transformer. The 11546-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 7 contracts

Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Service Agreement

Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2556

Appears in 6 contracts

Samples: Interconnection Agreement, Service Agreement, Service Agreement

Transformer. The 115-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then SERVICE AGREEMENT NO. 2550 both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 4 contracts

Samples: Standard Small Generator Interconnection Agreement, Service Agreement, Interconnection Agreement

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, SERVICE AGREEMENT NO. 2571 then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 4 contracts

Samples: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Transformer. The 115-34.5kV 115/34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 3 contracts

Samples: Interconnection Agreement, Service Agreement, Interconnection Agreement

Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, SERVICE AGREEMENT NO. 2573 then both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 3 contracts

Samples: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2554

Appears in 3 contracts

Samples: Service Agreement, Service Agreement, Service Agreement

Transformer. The 115-34.5kV 115–34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 2 contracts

Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

Transformer. The 115-34.5kV 115–34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 2 contracts

Samples: Interconnection Agreement, Standard Small Generator Interconnection Agreement

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2555

Appears in 2 contracts

Samples: Service Agreement, Service Agreement

AutoNDA by SimpleDocs

Transformer. The 115-34.5kV 34.5 kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.. SERVICE AGREEMENT NO. 2576

Appears in 2 contracts

Samples: Interconnection Agreement, Interconnection Agreement

Transformer. The 11569-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both SERVICE AGREEMENT NO. 2662 phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 2 contracts

Samples: Service Agreement, Service Agreement

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will All microprocessor differential relays shall have phase and ground time and instantaneous SERVICE AGREEMENT NO. 2647 overcurrent protection enabled. Transformer relay protection shall operate separate lockout relays to trip and block the necessary breakers.through a lockout

Appears in 2 contracts

Samples: Service Agreement, Service Agreement

Transformer. The 115230-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both differential relays with backup phase and ground time and instantaneous protection shall be providedovercurrent protection. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 1 contract

Samples: Interconnection Agreement

Transformer. The 11569-34.5kV transformer is protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will operate separate lockout relays to trip and block the necessary breakers.

Appears in 1 contract

Samples: Service Agreement

Transformer. The 115-34.5kV 34.5 kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous protection shall be provided. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 1 contract

Samples: Interconnection Agreement

Transformer. The 115-34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then both phase and ground time and instantaneous Transformer relay protection shall be providedoperate through a lockout (86) relay. Each of the two schemes will transformer protective relay shall operate separate its own dedicated lockout relays to trip and block the necessary breakersrelay.

Appears in 1 contract

Samples: Service Agreement

Transformer. The 115-34.5kV 69/34.5kV transformer is shall be protected by two independent protection systems; one must be a transformer differential. If overcurrent protection is used for the other system, then SERVICE AGREEMENT NO. 2574 both phase and ground time and instantaneous protection shall be provided. Transformer relay protection shall operate through a lockout (86) relay. Each of the two schemes will must operate separate lockout relays to trip and block the necessary breakers.

Appears in 1 contract

Samples: Standard Small Generator Interconnection Agreement