UPS System Sample Clauses

UPS System. Throughout the Term, Tenant shall have the non-exclusive right, at Tenant’s sole cost and expense, to use, maintain and operate the uninterruptible power supply systems (the “Existing UPS System”) in the Buildings (excluding the uninterruptible power supply system located in and serving the small telephone room) as reasonably necessary to furnish the uninterruptible power supply needs for the use of the Premises, subject to all of the applicable terms, covenants and provisions of this Lease. Tenant covenants and agrees that throughout the Term, Tenant shall maintain, replace, repair and operate the Existing UPS System at the sole cost and expense of Tenant and without any charge, cost or expense to Landlord. In connection with the maintenance, replacement, repair and operation of the Existing UPS System, Tenant shall comply with all Applicable Laws and shall procure, maintain and pay for all permits and licenses required therefore, including all renewals thereof. Tenant, at Tenant’s sole cost and expense, shall promptly repair any and all damage to the Buildings and to any part of the Project caused by or resulting from the maintenance, replacement, repair, operation or removal of the Existing UPS System by Tenant pursuant to the provisions of this Section 12.8, except to the extent that such maintenance, repair, replacement, operation or removal resulted in a casualty not caused by Tenant that caused such damage. All costs (if any) incurred by Landlord in connection with the Existing UPS System, including, without limitation, the maintenance and operation thereof, shall be paid by Tenant to Landlord, as Additional Rent, within thirty (30) days after Landlord’s demand therefore. LANDLORD MAKES NO WARRANTIES OF WHATSOEVER NATURE REGARDING THE EXISTING UPS SYSTEM, EXPRESS OR IMPLIED, IT BEING THE INTENTION OF LANDLORD AND TENANT EXPRESSLY TO NEGATE AND EXCLUDE ALL WARRANTIES AS BETWEEN LANDLORD AND TENANT. LANDLORD SHALL HAVE NO RESPONSIBILITY OR LIABILITY TO TENANT, ITS AGENTS, EMPLOYEES, CONTRACTORS, VISITORS OR INVITEES FOR, LOSSES, DAMAGES OR INJURY TO PERSONS OR PROPERTY CAUSED BY, RELATED TO, ARISING OUT OF OR IN CONNECTION WITH, THE USE OF, FAILURE, NON-PERFORMANCE OR INADEQUATE PERFORMANCE OF THE EXISTING UPS SYSTEM, AND TENANT HEREBY RELEASES LANDLORD FROM ANY AND ALL LIABILITY FOR SUCH LOSSES, DAMAGES OR INJURY, EXCEPT FOR ANY SUCH LOSSES, DAMAGE OR INJURY CAUSED BY THE GROSS NEGLIGENCE OR WILLFUL MISCONDUCT OF LANDLORD OR ANY OF ITS AGENTS, CONTRA...
AutoNDA by SimpleDocs
UPS System. Tenant shall be permitted to have the exclusive use of one of the existing UPS systems in the Building.
UPS System. Subject to Landlord's written consent and approval of all plans and specifications for the location, installation, and all other aspects thereof and compliance with all applicable laws and code in installation, operation, and maintenance, Tenant shall be permitted to install an uninterrupted power source system and emergency stand-by battery system, above ground fuel tank, and generator on the Project in a mutually acceptable location.
UPS System. 5. The entire building is equipped with fire and smoke detection systems.
UPS System. For the continuous operation of the IT-system aa UPS-system must be provided (refer to Appendix 3). The UPS in the primary server rooms shall be linked with the UPS in the redundant back up-server room. Booth UPS must be fed by the terminal grid so as by the genset. Automatic transfer switches executed as static switches shall secure the connection between the feeders so as between the systems. The UPS in each server room shall be executed as (n+1) - redundancy system. It must ensure all essential operations of the server room equipment. Any restrictions in case of maintenance of UPS-block or grid failure are not allowed. The following typical qualities, functions and dimensions of a standard UPS shall be observed as minimum requirements. The use of other type of equipment may be permitted on the basis of documented evidence of conformity of electrical, mechanical, functional and thermal characteristics; the comparison chart and specification has to be provided by the Contractor for Engineer’s approval. - Nominal power 15 kVA, backup time 36 minutes; - Online-UPS according Class VFI-SS-111 IEC-EN 62040-; - Real online, double conversion, galvanic separation, parallel redundant operation Description The UPS shall consist of three ups blocks in parallel operation (n+1)-redundancy Each UPS-block consists of: - Rectifier for feeding the inverter and charging / trickle charging the battery; - Transistor inverter in PWM technology with sine wave output; - Output transformer with galvanic separation; - Static electronic bypass-switch; - Manual bypass switch for maintenance; - Multifunction panel with operating parts, digital measurements and UPS-status and alarm display; - Maintenance free lead acid battery, valve regulated. Standards VDE, DIN, EN, SEV, IEC, CE, ISO 9001, manufacturing according to IEC-EN 50091 / 62040 Documentation Manual in English and Vietnamese language Technical data per UPS block Output power : 15 kVA (cos phi 0,7) Input voltage : 230 / 400 V, 3 ph., ± 10%, 50 Hz ± 5%, N, PE Input power : 15,9 kVA Input current nominal/maximum : 23/31 A Required main fuse : 35 A Required cable size rectifier input/output : 10/6 mm² Required cable size battery : 16 mm² Output voltage : 230/400 V, 3 ph., ± 1% static, ± 5% dynamic Output frequency : 50 Hz ± 0,25-3 % (adjustable range) at mains controlled operation, 50 Hz ± 0,001 % at battery operation Overload capability : 125% for 10 minutes/150% for 1 minute/ 200% for 100ms Efficiency : 91 % Heat losses : 1,...
UPS System. Landlord will make available the existing uninterrupted power supply (“UPS”) system in as-is condition for Tenant’s use. Landlord makes no representation or warranty as to the condition or usability of the UPS system. At Tenant’s request at any time prior to the Commencement Date, Landlord shall remove and dispose of the UPS system.
UPS System. Landlord and Tenant acknowledge that there is an uninterruptible power supply unit and associated HVAC unit and equipment (collectively, the “UPS System”) located in a mechanical room within the Binney Premises. From and after the Binney Term Commencement Date, Tenant shall have the exclusive right to use the UPS System throughout the Lease Term. Tenant acknowledges that neither Landlord nor any agent of Landlord has made any representation or warranty with respect to the condition of the UPS System, or with respect to the suitability of the UPS System for the conduct of Tenant’s business under the Lease. Tenant acknowledges that it is fully familiar with the condition of the UPS System and agrees to take the same in its condition “as is” as of the Binney Term Commencement Date, and that Landlord shall have no obligation to repair, maintain or monitor the UPS System during the Binney Term, and that Landlord shall have no liability for any failure of the UPS System (or any utility or service serving the UPS) during the Term. Landlord and Tenant agree that that the UPS System is affixed to the Binney Premises, and that Landlord will own the UPS System upon the expiration of the Binney Term.
AutoNDA by SimpleDocs
UPS System. Tenant may maintain an uninterrupted power system in the Premises (including back-up batteries) (collectively, the “UPS System”) at a location reasonably acceptable to Landlord, provided that the installation, maintenance and use thereof complies with Law and such installation is made in accordance with plans and specifications therefor that have been approved by Landlord. Tenant shall maintain the UPS System in good repair and condition and maintain and operate the UPS System in accordance with Laws. Tenant shall, and at Landlord’s request and Tenant’s sole risk and expense, remove the UPS System (including all piping, wiring, fixtures related thereto), within 30 days after the occurrence of any of the following events: (1) the termination of Tenant’s right to possess the Premises; (2) the termination of the Lease; (3) the expiration of the Term; or (4)
UPS System. DLR performs daily visual inspections to check for any anomalies on the UPS units and batteries. Inspections are performed twice a year, as per OEM recommendation.
UPS System. The Tenant shall be allowed to install a UPS system (the “UPS System”) inside the Leased Premises. Upon the expiration or earlier termination of this Lease, the Tenant shall, at the Tenant's expense, remove the UPS System and repair any damage to the Leased Premises caused thereby. Tenant’s right to install the UPS System is subject to the following terms and conditions:
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!