UPS System Sample Clauses

UPS System. The entire building is equipped with fire and smoke detection systems.
AutoNDA by SimpleDocs
UPS System. Subject to Landlord's written consent and approval of all plans and specifications for the location, installation, and all other aspects thereof and compliance with all applicable laws and code in installation, operation, and maintenance, Tenant shall be permitted to install an uninterrupted power source system and emergency stand-by battery system, above ground fuel tank, and generator on the Project in a mutually acceptable location.
UPS System. Tenant shall be permitted to have the exclusive use of one of the existing UPS systems in the Building.
UPS System. Landlord agrees that Tenant, at its sole cost and expense, and subject to compliance with the provisions of this Section 10.11, shall have the right to install and operate during the term an emergency electrical generator fueled by natural gas (which is separately metered to the Premises and paid for directly by Tenant to the gas supplier) on the Property in the location shown on Exhibit G attached hereto, and to run cables and lines from the generator to the Premises using the common shafts, chases, and conduits of the Building intended for such purpose to the extent that the same may be available after meeting Landlord’s requirements for the Building, (the emergency generator and associated conduit, cables and lines (both interior and exterior) are hereinafter referred to collectively as the “UPS System”). The UPS System shall provide emergency back-up power to the Premises only, and no other party shall make use of the UPS System. {B2323618; 13} Tenant shall prepare plans and specifications for the UPS System in accordance with the requirements of Exhibit C, which plans and specifications shall be subject to review and approval by Landlord as provided in Exhibit C; provided, however, that Landlord hereby approves the specifications attached hereto as Exhibit G-1; provided further however, that notwithstanding such specifications the UPS System shall be fueled by natural gas. Upon final approval by Landlord of Tenant’s plans for the UPS System, Tenant may install the UPS System in accordance with the requirements of Exhibit C, any requirements of Landlord’s insurance carrier(s), and all other applicable provisions of this Lease including, without limitation, those of Subsection 6.2.5. Landlord shall have no obligation or make any alterations, repairs or replacements to any portion of the Building or Property in order to accommodate the installation or operation of the UPS System. During the term, Tenant, at its sole cost and expense, shall performs all repairs and maintenance required to keep the UPS System in good working order, appearance and condition, and Tenant shall promptly repair any damage to the Building or Property caused by the installation or operation of the UPS System. Tenant shall operate the UPS System in compliance with all applicable codes, laws, rules and regulations. Tenant may not relocate the UPS System and Tenant may not modify any portion of the UPS System without, in each instance, obtaining Landlord’s prior written approval to ...
UPS System. 10 3.9 Telco .......................................................... 11 3.10
UPS System. The Tenant shall be allowed to install a UPS system (the “UPS System”) inside the Leased Premises. Upon the expiration or earlier termination of this Lease, the Tenant shall, at the Tenant's expense, remove the UPS System and repair any damage to the Leased Premises caused thereby. Tenant’s right to install the UPS System is subject to the following terms and conditions: (a) The Tenant shall be solely responsible for all costs associated with the installation, use and maintenance of the UPS System; (b) As of the Effective Date, there is a designated area for high density storage on each floor of the Building, which has a live load capacity of 150 pounds per square foot. The Landlord does not anticipate a need to reinforce the structure to accommodate the Tenant’s UPS System, but reserves the right to engage the Landlord’s architect and/or structural engineer for review of the UPS System specifications to ensure that the UPS System shall not adversely affect the electrical or any other system of the Building; and (c) Upon the expiration or earlier termination of the Lease, Tenant shall repair any damage caused to the Leased Premises or to any portion of the Building resulting from the installation and/or removal of the UPS System. The terms of this Special Stipulation No. VII shall survive the expiration or earlier termination of this Lease.
UPS System. For the continuous operation of the IT-system aa UPS-system must be provided (refer to Appendix 3). The UPS in the primary server rooms shall be linked with the UPS in the redundant back up-server room. Booth UPS must be fed by the terminal grid so as by the genset. Automatic transfer switches executed as static switches shall secure the connection between the feeders so as between the systems. The UPS in each server room shall be executed as (n+1) - redundancy system. It must ensure all essential operations of the server room equipment. Any restrictions in case of maintenance of UPS-block or grid failure are not allowed. The following typical qualities, functions and dimensions of a standard UPS shall be observed as minimum requirements. The use of other type of equipment may be permitted on the basis of documented evidence of conformity of electrical, mechanical, functional and thermal characteristics; the comparison chart and specification has to be provided by the Contractor for Engineer’s approval. - Nominal power 15 kVA, backup time 36 minutes; - Online-UPS according Class VFI-SS-111 IEC-EN 62040-; - Real online, double conversion, galvanic separation, parallel redundant operation The UPS shall consist of three ups blocks in parallel operation (n+1)-redundancy Each UPS-block consists of: - Rectifier for feeding the inverter and charging / trickle charging the battery; - Transistor inverter in PWM technology with sine wave output; - Output transformer with galvanic separation; - Static electronic bypass-switch; - Manual bypass switch for maintenance; - Multifunction panel with operating parts, digital measurements and UPS-status and alarm display; - Maintenance free lead acid battery, valve regulated. Standards VDE, DIN, EN, SEV, IEC, CE, ISO 9001, manufacturing according to IEC-EN 50091 / 62040 Manual in English and Vietnamese language Output power : 15 kVA (cos phi 0,7) Input voltage : 230 / 400 V, 3 ph., ± 10%, 50 Hz ± 5%, N, PE Input power : 15,9 kVA Input current nominal/maximum : 23/31 A Required main fuse : 35 A Required cable size rectifier input/output : 10/6 mm² Required cable size battery : 16 mm² Output voltage : 230/400 V, 3 ph., ± 1% static, ± 5% dynamic Output frequency : 50 Hz ± 0,25-3 % (adjustable range) at mains controlled operation, 50 Hz ± 0,001 % at battery operation Overload capability : 125% for 10 minutes/150% for 1 minute/ 200% for 100ms Efficiency : 91 % Heat losses : 1,04 kW Noise level : less than 52 dB (A) Distortion outp...
AutoNDA by SimpleDocs
UPS System. Landlord will make available the existing uninterrupted power supply (“UPS”) system in as-is condition for Tenant’s use. Landlord makes no representation or warranty as to the condition or usability of the UPS system. At Tenant’s request at any time prior to the Commencement Date, Landlord shall remove and dispose of the UPS system.
UPS System. Tenant may maintain an uninterrupted power system in the Premises (including back-up batteries) (collectively, the “UPS System”) at a location reasonably acceptable to Landlord, provided that the installation, maintenance and use thereof complies with Law and such installation is made in accordance with plans and specifications therefor that have been approved by Landlord. Tenant shall maintain the UPS System in good repair and condition and maintain and operate the UPS System in accordance with Laws. Tenant shall, and at Landlord’s request and Tenant’s sole risk and expense, remove the UPS System (including all piping, wiring, fixtures related thereto), within 30 days after the occurrence of any of the following events: (1) the termination of Tenant’s right to possess the Premises; (2) the termination of the Lease; (3) the expiration of the Term; or (4)
UPS System. DLR performs daily visual inspections to check for any anomalies on the UPS units and batteries. Inspections are performed twice a year, as per OEM recommendation.
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!