Common use of Wiring Clause in Contracts

Wiring. All wiring for space heaters shall be done with insulated stranded copper conductor of not less than 2.5 sqmm cross section. Each wire shall be identified at both ends with wire designation as per contractor‟s wiring diagram and shall be brought out to a terminal box outside the bus duct.

Appears in 3 contracts

Samples: Zonal Rate Contract for Petty Electrical Works, Zonal Rate Contract for Petty Electrical Works, Zonal Rate Contract for Petty Electrical Works

AutoNDA by SimpleDocs

Wiring. 10.1 All wiring for space heaters shall be done with insulated stranded copper conductor of not less than 2.5 sqmm cross section. Each wire shall be identified at both ends with wire designation as per contractor‟s wiring diagram and shall be brought out to a terminal box outside the bus duct. a. Terminal blocks shall be box-clamp type Elemex 10 sqmm with marking strips or approved equal. b. At least 20% spare terminals shall be furnished in the terminal block.

Appears in 1 contract

Samples: Zonal Rate Contract for Petty Electrical Works