Dampers they shall be of stock-bridge or spacer-damper type, depending on the configuration of the bundle of conductors to control the wind vibration levels within the safety limits allowed; maintaining their mechanical and damping properties through the line service life
Dampers they shall be of stock-bridge type to control the wind vibration levels within the safety limits allowed; maintaining their mechanical and damping properties through the line service life.
Dampers o Check for proper operation and adjust/repair as needed (semi- annually) o Lubricate dampers, linkage, etc.
Dampers. All mechanical work on boiler plant dampers including removal, repairs, installation and testing (stroking) inclusive of: All Primary Air (PA) Dampers Secondary Air dampers Core air dampers Mill bypass dampers All air heater dampers All Forced Draught (FD) Fan dampers (excluding Radial Vane Control i.e. RVCs) All Induced Draught (ID) Fan Dampers
Dampers a. Dampers: All duct dampers shall be opposed blade louver dampers of robust 16 G GSS construction and tight fitting. The design, method of handling and control shall be suitable for the location and service required.
Dampers v) Checking of Plug, Switches and other connections against tightness with special reference to earthing.
Dampers. (aa) Refer to Schedules for dimensions on HD-06. (bb) Refer to Details for arrangement 17-HD-07.
Dampers. All types of Dampers, including Automatic Dampers and Multi-Zone Dampers, Manual Control Dampers and Fire Control Dampers, except Patented Pressure Reducing Devices.
Dampers. A. The Building Automation System supplier shall provide all automatic control dampers not specified to be supplied integral to the HVAC equipment.
B. Dampers shall be low leakage or high velocity low leakage air foil as specified in the sequence of operation or in the equipment specifications and schedules. All proportional dampers shall be opposed blade type, except mixing dampers shall be parallel type. Two position dampers may be opposed or parallel blade type.
C. Damper frames and blades shall be galvanized steel and a minimum of 16 gauge. Blade width shall not exceed 8 inches. Dampers and seals shall be suitable for temperature ranges of -50°F to 250°F.
D. Blades: 14-gauge, or 16-gauge air foil shaped, double, galvanized steel or extruded aluminum.
E. Bearings: Nylon or oil impregnated.
Dampers. Provide fire-rated dampers at all fire-rated partitions. Provide smoke dampers at all smoke sealed partitions. Division 16 (16.1 – 16.9): Wiring Devices and Electrical Requirements
16.1 Provide separate electrical panel for Server Room.
16.2 Provide any additional electrical panels required to realize plan.
16.3 All receptacles to be building standard device and cover plate color match Building Standard.
16.4 Hardwire new electric hot water heaters per note 15.4
16.5 Receptacles as indicated: