Grounding. A. The conduit system supports, cabinets, switchboards, etc., and neutral conductors must be permanently and effectively grounded by means of approved ground clamp, in accordance with the electrical safety orders of the Department of Industrial Relations of the State of California. B. This Contractor shall exercise every precaution to obtain good contacts at all panel boxes, pull boxes, etc. Where it is not possible to obtain good contacts, the conduit shall be bonded around the boxes with a #6B&S gauge, rubber covered, double braided wire with ground clamps. C. Equipment and raceway bonding procedures shall be rigidly maintained and meet all jurisdictional requirements of codes and regulations. D. A separate grounding conductor shall be run in all PVC conduit runs.