Interconnection Points and Cables Sample Clauses

Interconnection Points and Cables. 12.8.1 CBT shall provide CLEC an Interconnection point or points physically accessible by both CBT and CLEC, at which the fiber optic cable (or other necessary facility as per CLEC's Bona Fide Request) carrying CLEC's circuits can enter CBT's Premises; provided that CBT shall designate Interconnection Points as close as reasonably possible to CBT's Premises. 12.8.2 CBT shall provide at least two (2) such Interconnection points at CBT's Premises at which there are at least two (2) entry points for CLEC's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points.
AutoNDA by SimpleDocs
Interconnection Points and Cables. Ameritech shall: XII.7.1 provide Requesting Carrier an Interconnection point or points physically accessible by both Ameritech and Requesting Carrier, at which the fiber optic cable carrying Requesting Carrier’s circuits can enter Ameritech’s Premises; provided that Ameritech shall designate Interconnection Points as close as reasonably possible to Ameritech’s Premises; XII.7.2 provide at least two (2) such Interconnection points at Ameritech’s Premises at which there are at least two (2) entry points for Requesting Carrier’s cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; and XII.7.3 permit Requesting Carrier Interconnection of copper or coaxial cable if such Interconnection is first approved by the Commission.
Interconnection Points and Cables. SBC-AMERITECH shall: 12.8.1 Provide CLEC an Interconnection point or points physically accessible by both SBC-AMERITECH and CLEC, at which the fiber optic cable carrying CLEC's circuits can enter SBC-AMERITECH's Premises; provided that SBC-AMERITECH shall designate Interconnection Points as close as reasonably possible to SBC-AMERITECH's Premises; 12.8.2 Provide at least two (2) such Interconnection points at SBC- AMERITECH's Premises at which there are at least two (2) entry points for CLEC's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; 12.8.3 Permit CLEC Interconnection of copper or coaxial cable if such Interconnection is first approved by the Public Service Commission of Wisconsin, or its designee; and 12.8.4 Permit CLEC Physical Collocation of equipment associated with microwave entrance facilities to Collocation, to the same extent SBC-AMERITECH permits physical Collocation arrangements to itself, affiliates or other Carriers. Where Physical Collocation of equipment associated with microwave entrance facilities to Collocation is not technically feasible, SBC-AMERITECH shall provide Virtual Collocation of such facilities as required where technically feasible. Microwave entrance facilities include microwave antenna(s), mounting structure and waveguide or coax used to extend radio signal to Collocation area. The external apparatus may include some low power microwave antennas with integrated radio equipment which is powered by DC voltage that is simplexed over coax transmission cable. Separate transmission and receiving radio equipment will not be allowed to be placed externally to the Collocation area. 12.8.5 Permit CLEC to link its collocation cages to its other collocation cages located in the same central office without purchasing a cross-connect. If the cages are separated by other SBC-AMERITECH designated space, CLEC will be permitted to run cabling, limited only by SBC-AMERITECH’s reasonable safety and network security requirements that it imposes on itself on SBC-AMERITECH provided and designated cabling racks.
Interconnection Points and Cables. Ameritech shall: XII.8.1 provide Requesting Carrier an Interconnection point or points physically accessible by both Ameritech and Requesting Carrier, at which the fiber optic cable carrying Requesting Carrier's circuits can enter Ameritech's Premises; provided that Ameritech shall designate Interconnection Points as close as reasonably possible to Ameritech's Premises; XII.8.2 provide at least two (2) such Interconnection points at Ameritech's Premises at which there are at least two (2) entry points for Requesting Carrier's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; XII.8.3 permit Requesting Carrier Interconnection of copper or coaxial cable if such Interconnection is first approved by the Commission; and XII.8.4 permit Requesting Carrier Physical Collocation of microwave transmission facilities, except where such Collocation is not practical for technical reasons or because of space limitations, in which case Ameritech shall provide Virtual Collocation of such facilities as required where technically feasible.
Interconnection Points and Cables. XII.8.1 Ameritech shall: 12.8.1.1 provide CLEC an Interconnection point or points physically accessible by both Ameritech and CLEC, at which the fiber optic cable carrying CLEC's circuits can enter Ameritech's Premises; provided that Ameritech shall designate Interconnection Points as close as reasonably possible to Ameritech's Premises; 12.8.1.2 provide at least two (2) such Interconnection points at Ameritech's Premises at which there are at least two (2) entry points for CLEC's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; 12.8.1.3 permit CLEC Interconnection of copper or coaxial cable if such Interconnection is first approved by the Commission; and 12.8.1.4 permit CLEC Physical Collocation of microwave transmission facilities, except where such Collocation is not practical for technical reasons or because of space limitations, in which case Ameritech shall provide Virtual Collocation of such facilities as required where technically feasible. XII.8.2 When CLEC and Ameritech are located in a "condo" building, CLEC shall be allowed to locate, in CLEC's Wire Center, equipment that normally would have been Collocated in Ameritech's Wire Center to enable CLEC to access Ameritech's unbundled Network Elements. Such equipment will be connected to Ameritech's unbundled Network Elements through a mid-span meet arrangement at the DSO, DS1, DS3, OC3, OC12, OC48 and where available, STS-1 rates, subject to any technical limitations on the distance between Wire Centers. CLEC will pay all costs (as defined in Section 252(d) of the Act) relating to any such mid-span meet arrangement and will also be responsible for the connection between CLEC's Wire Center and Ameritech's facilities.
Interconnection Points and Cables. Ameritech shall:
Interconnection Points and Cables. AT&T shall: 31.4.1 provide Ameritech an Interconnection point or points physically accessible by both Ameritech and AT&T, at which the fiber optic cable carrying Ameritech's circuits can enter AT&T’s Premises; provided that AT&T shall designate Interconnection Points as close as reasonably possible to AT&T’s Premises; 31.4.2 provide at least two (2) such Interconnection points at AT&T’s Premises at which there are at least two (2) entry points for Ameritech's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; and 31.4.3 permit Ameritech Interconnection of copper or coaxial cable if such Interconnection is fast approved by the Commission.
AutoNDA by SimpleDocs
Interconnection Points and Cables. CBT shall: 12.8.1 provide Sprint an Interconnection point or points physically accessible by both CBT and Sprint, at which the fiber optic cable (or other necessary facility as per Sprint's Bona Fide Request) carrying Sprint's circuits can enter CBT's Premises; provided that CBT shall designate Interconnection Points as close as reasonably possible to CBT's Premises; 12.8.2 provide at least two (2) such Interconnection points at CBT's Premises at which there are at least two (2) entry points for Sprint's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points;
Interconnection Points and Cables. Ameritech shall: XII.8.1 provide Focal an Interconnection point or points physically accessible by both Ameritech and Focal, at which the fiber optic cable carrying Focal's circuits can enter Ameritech's Premises; provided that Ameritech shall designate Interconnection Points as close as reasonably possible to Ameritech's Premises; XII.8.2 provide at least two (2) such Interconnection points at Ameritech's Premises at which there are at least two (2) entry points for Focal's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points; XII.8.3 permit Focal Interconnection of copper or coaxial cable if such Interconnection is first approved by the Commission; and XII.8.4 permit Focal Physical Collocation of microwave transmission facilities, except where such Collocation is not practical for technical reasons or because of space limitations, in which case Ameritech shall provide Virtual Collocation of such facilities as required where technically feasible.
Interconnection Points and Cables. CBT shall: 12.8.1 provide Adelphia an Interconnection point or points physically accessible by both CBT and Adelphia, at which the fiber optic cable (or other necessary facility as per Xxxxxxxx's Bona Fide Request) carrying Xxxxxxxx's circuits can enter CBT's Premises; provided that CBT shall designate Interconnection Points as close as reasonably possible to CBT's Premises; 12.8.2 provide at least two (2) such Interconnection points at CBT's Premises at which there are at least two (2) entry points for Adelphia's cable facilities, and at which space is available for new facilities in at least two (2) of those entry points;
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!