Common use of Connecting Transmission Owner’s Attachment Facilities Clause in Contracts

Connecting Transmission Owner’s Attachment Facilities. The Connecting Transmission Owner’s Attachment Facilities include all facilities between the Point of Change of Ownership and the Point of Interconnection. The Connecting Transmission Owner’s Attachment Facilities will contain the revenue metering units, one (1) 115 kV disconnect switch and the necessary 115 kV bus work and structures to connect the new Point of Interconnection substation, known as the Xxxxxxx Xxxx Substation, with the Developer’s Attachment Facilities. This includes the following major electrical and physical equipment: Three (3) 115 kV, 1200A, TPST, vert. brk. w/arc. horns disconnect switches Three (3) Meter Combo Units CT/VT 115kV, 600/300:5 MA; Grounding materials; Conduit and trench; Control cabling; 115 kV Bus work; and 115 kV Structures. The Connecting Transmission Owner’s Attachment Facilities shall be designed, procured, and constructed by the Developer. The Connecting Transmission Owner shall perform design reviews, construction supervision, and testing of the Connecting Transmission Owner’s Attachment Facilities.

Appears in 4 contracts

Samples: Large Generator Interconnection Agreement, Agreement, Agreement

AutoNDA by SimpleDocs
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!