Reactive Power 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New York Control Area on a comparable basis. 1.8.2 The NYISO is required to pay the Interconnection Customer for reactive power, or voltage support service, that the Interconnection Customer provides from the Small Generating Facility in accordance with Rate Schedule 2 of the NYISO Services Tariff.
Power Factor Design Criteria (Reactive Power A wind generating plant shall maintain a power factor within the range of 0.95 leading to 0.95 lagging, measured at the Point of Interconnection as defined in this LGIA, if the ISO’s System Reliability Impact Study shows that such a requirement is necessary to ensure safety or reliability. The power factor range standards can be met using, for example without limitation, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors if agreed to by the Connecting Transmission Owner for the Transmission District to which the wind generating plant will be interconnected, or a combination of the two. The Developer shall not disable power factor equipment while the wind plant is in operation. Wind plants shall also be able to provide sufficient dynamic voltage support in lieu of the power system stabilizer and automatic voltage regulation at the generator excitation system if the System Reliability Impact Study shows this to be required for system safety or reliability.
Reactive Power and Primary Frequency Response 9.6.1 Power Factor Design Criteria
Payment for Reactive Power NYISO shall pay Developer for reactive power or voltage support service that Developer provides from the Large Generating Facility in accordance with the provisions of Rate Schedule 2 of the NYISO Services Tariff.
CHARACTERISTICS OF THE ACADEMY The characteristics of the Academy set down in Section 1(6) of the Academies Act 2010, are that:
ODUF Physical File Characteristics 6.2.1 ODUF will be distributed to TWTC via Secure File Transfer Protocol (FTP). The ODUF feed will be a variable block format. The data on the ODUF feed will be in a non-compacted EMI format (175 byte format plus modules). It will be created on a daily basis Monday through Friday except holidays. Details such as dataset name and delivery schedule will be addressed during negotiations of the distribution medium. There will be a maximum of one dataset per workday per OCN. If AT&T determines the Secure FTP Mailbox is nearing capacity levels, AT&T may move the customer to CONNECT: Direct file delivery. 6.2.2 If the customer is moved, CONNECT: Direct data circuits (private line or dial-up) will be required between AT&T and TWTC for the purpose of data transmission. Where a dedicated line is required, TWTC will be responsible for ordering the circuit, overseeing its installation and coordinating the installation with AT&T. TWTC will also be responsible for any charges associated with this line. Equipment required on the AT&T end to attach the line to the mainframe computer and to transmit messages successfully on an ongoing basis will be negotiated on an individual case basis. Any costs incurred for such equipment will be TWTC's responsibility. Where a dial-up facility is required, dial circuits will be installed in the AT&T data center by AT&T and the associated charges assessed to TWTC. Additionally, all message toll charges associated with the use of the dial circuit by TWTC will be the responsibility of TWTC. Associated equipment on the AT&T end, including a modem, will be negotiated on an individual case basis between the Parties. All equipment, including modems and software, that is required on TWTC end for the purpose of data transmission will be the responsibility of TWTC. 6.2.3 If TWTC utilizes FTP for data file transmission, purchase of the FTP software will be the responsibility of TWTC.
Characteristics The Contracts have the following characteristics: (i) all the Contracts are secured by Motorcycles; (ii) no Contract has a remaining maturity of more than 84 months; and (iii) the final scheduled payment on the Contract with the latest maturity is due no later than July 27, 2030. Approximately 63.90% of the Pool Balance as of the Cutoff Date is attributable to loans for purchases of new Motorcycles and approximately 36.10% is attributable to loans for purchases of used Motorcycles. No Contract was originated after the Cutoff Date. No Contract has a Contract Rate less than 0.010%.
Cloud Computing State Risk and Authorization Management Program In accordance with Senate Bill 475, Acts 2021, 87th Leg., R.S., pursuant to Texas Government Code, Section 2054.0593, Contractor acknowledges and agrees that, if providing cloud computing services for System Agency, Contractor must comply with the requirements of the state risk and authorization management program and that System Agency may not enter or renew a contract with Contractor to purchase cloud computing services for the agency that are subject to the state risk and authorization management program unless Contractor demonstrates compliance with program requirements. If providing cloud computing services for System Agency that are subject to the state risk and authorization management program, Contractor certifies it will maintain program compliance and certification throughout the term of the Contract.
Individual Characteristics Each Receivable has the following individual characteristics as of the Cut-Off Date: (i) each Receivable is secured by a new or used automobile, minivan or sport utility vehicle; (ii) each Receivable has an APR of no less than 0.00% and not more than 13.94; (iii) each Receivable had an original term to maturity of not more than 72 months and not less than 18 months and each Receivable has a remaining term to maturity, as of the Cut-Off Date, of 12 months or more; (iv) each Receivable has an Outstanding Principal Balance as of the Cut-Off Date of greater than or equal to $2,394.67; (v) no Receivable has a scheduled maturity date later than October 7, 2020; (vi) no Receivable was more than 30 days past due as of the Cut-Off Date; (vii) as of the Cut-off Date, no Receivable was noted in the records of VCI or the Servicer as being the subject of any pending bankruptcy or insolvency proceeding; (viii) no Receivable is subject to a force-placed Insurance Policy on the related Financed Vehicle; (ix) each Receivable is a Simple Interest Receivable; (x) each of the Receivables were selected using selection procedures that were not known or intended by VCI or the Servicer to be adverse to the Purchaser; and (xi) the Dealer of the Financed Vehicle has no participation in, or other right to receive, any proceeds of such Receivable.
Physical File Characteristics 7.2.1 The EODUF feed will be distributed to Comcast Phone over their existing Optional Daily Usage File (ODUF) feed. The EODUF messages will be intermingled among Comcast Phone’s Optional Daily Usage File (ODUF) messages. The EODUF will be a variable block format (2476) with an LRECL of 2472. The data on the EODUF will be in a non-compacted EMI format (175 byte format plus modules). It will be created on a daily basis (Monday through Friday except holidays). 7.2.2 Data circuits (private line or dial-up) may be required between BellSouth and Comcast Phone for the purpose of data transmission. Where a dedicated line is required, Comcast Phone will be responsible for ordering the circuit, overseeing its installation and coordinating the installation with BellSouth. Comcast Phone will also be responsible for any charges associated with this line. Equipment required on the BellSouth end to attach the line to the mainframe computer and to transmit successfully ongoing will be negotiated on an individual case basis. Where a dial-up facility is required, dial circuits will be installed in the BellSouth data center by BellSouth and the associated charges assessed to Comcast Phone. Additionally, all message toll charges associated with the use of the dial circuit by Comcast Phone will be the responsibility of Comcast Phone. Associated equipment on the BellSouth end, including a modem, will be negotiated on an individual case basis between the Parties. Version 4Q01 12/01/01 All equipment, including modems and software, that is required on Comcast Phone’s end for the purpose of data transmission will be the responsibility of Comcast Phone.