Women's Only. The toilet is inaccessible because its centerline is 23 ½ inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.
Women's Only. There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig.
Women's Only. The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
Women's Only b) The soap dispenser located over the lavatories is 49 ½ inches above the finished floor and requires a forward reach. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
c) The coin slot to the sanitary napkin dispenser is 55 ½ inches above the finished floor. Provide a sanitary napkin dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
Women's Only. (1) The toilet room door is inaccessible because the pressure required to open the door is greater than 5 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
Women's Only a) The toilet room door has knob hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards §§ 4.13.5, 4.13.9.
b) The paper towel dispenser is inaccessible because the controls are mounted at 70 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
Women's Only a) The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
Women's Only a) The route through the locker room is inaccessible because the air dryer is a protruding object that would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
b) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
Women's Only a) The lavatory is inaccessible because it lacks clear floor space. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards § 4.19.3, Fig. 32.
b) The lavatory is inaccessible because the hardware requires twisting of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
c) The air dryer protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
d) In the toilet stall for persons with disabilities, there is no rear grab bar. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
Women's Only. The path of travel into the room is reduced to 31 inches wide between the lavatories and the paper towel/trash receptacle. Provide an accessible route through the toilet room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.