Minimum space requirement for key areas Sample Clauses
Minimum space requirement for key areas. The Concessionaire shall design and construct the Hospital Building in accordance with the minimum area requirements specified below. For the avoidance of doubt, the Concessionaire shall be free to provide for a greater area for any of the below mentioned facilities. Front office waiting space Higher of 400 Sq. Ft or 1 sq.ft. per visitor Counter working space and circulation space 65 sq.ft. Receptionist counter 1.2 mt long Floor space for ICU beds 269 to 323 sq.ft. per bed (this includes support services) Floor space for paediatric ICU beds 108 to 129 sq.ft. per bed Floor space for high dependency unit 215 to 258 sq.ft. per bed Floor space for general ▇▇▇▇ 161 to 194 sq.ft. per bed Minimum distance between centres of two beds 2.5 mt. Minimum clearance at foot end of each bed 1.2 mt. Minimum area for apertures (windows/ventilators) 20% of the floor area (if on same wall) 15% of the floor area (if on opposite walls) Corridors width a. General atleast 2.4 mt. wide b. For OT area only 2.85 mt wide Clear roof height in general 3.6 mt measured at any point from floor to roof General operation theatre (OT) 32 ▇▇.▇▇. Lithotripsy - procedure cum operating room (without need for anaesthesia) 24 ▇▇.▇▇ Minimum distance between centres of two ICU beds 3.5 mt. Minimum clearance between head of bed to the wall 0.25 mt. Minimum floor space per bed in a ▇▇▇▇/ room (excluding allowance for support services, bathroom, etc.) 7 ▇▇.▇▇. Minimum floor space per bed in emergency/ acute ▇▇▇▇/ rooms (excluding allowance for support services, bathroom, etc.) 10.5 ▇▇.▇▇. Minimum floor space per bed in isolation ▇▇▇▇/ rooms (excluding allowance for support services, bathroom, etc.) 12 ▇▇.▇▇. Minimum floor space per bed in ICU ▇▇▇▇/ rooms (excluding allowance for support services, bathroom, etc.) 20 ▇▇.▇▇. CSSD {For Bed Capacity of 100: 70 ▇▇.▇▇. For Bed Capacity of 200: 140 ▇▇.▇▇.} Pharmaceutical and consumable stores {For Bed Capacity of 100: 50 ▇▇.▇▇. For Bed Capacity of 200: 100 ▇▇.▇▇.}1 Mortuary 50 ▇▇.▇▇. Clear roof height for OT 4 m. measured at any point from floor to roof Super speciality OT (operating room area) for orthopaedics (with C-Arm/ fluoroscopy unit), cardiology (with cath lab), CTVS, neurosurgery and other tertiary care interventions 58 ▇▇.▇▇. or 625 Sq.ft. per operating room (assuming one Table per operating room) Other space requirements for OT: zoning required 1. Protective zone: Includes reception, waiting area, trolley bay, changing room 2. Clean zone: Includes p...