Phase Unbalance Sample Clauses

Phase Unbalance. User's facility and / or equipment and switchgear parts of fields, the limit values ​​specified in the relevant legislation that may arise due to instability of the waveform distortion of the phase shall be designed to withstand Transmission system and / or a User-owned facility planned to out of service to be occurred with phase instabilities , the harmonic components does not exceed 2% of the total, and no often and short duration may be allowed with the approval of the TEIAS.
AutoNDA by SimpleDocs
Phase Unbalance. The Facility shall limit unbalanced current injection levels such that voltage unbalance is maintained per IEC 00000-0-00, as such standard may be revised, modified, or replaced from time to time. Interconnection Customer is responsible for protecting its Facility from inadvertent phase unbalance or single phasing in the TVA transmission system’s voltage.
Phase Unbalance. The weekly 95 percentile of Phase (Voltage) Unbalance, calculated in accordance with IEC61000-4-30 and IEC61000-3-13, on the CEB System shall be less than or equal to 1.3% unless abnormal conditions prevail. The Phase Unbalance shall be calculated from the ratio of root mean square (rms) of negative phase sequence voltage to rms of positive phase sequence voltage, based on 10-minute average values, in accordance with IEC 00000-0-00.
Phase Unbalance. The LSP generator shall not cause phase current unbalance greater than 10 percent.
Phase Unbalance. The weekly 95 percentile of Phase (Voltage) Unbalance, calculated in accordance with IEC61000-4-30 and IEC61000-3-13, on the CEB System shall be less than or equal to 1.3% unless abnormal conditions prevail. The Phase Unbalance shall be calculated from the ratio of root mean square (rms) of negative phase sequence voltage to rms of positive phase sequence voltage, based on 10-minute average values, in accordance with IEC 00000-0-00. The Facility shall be at least capable of operating at any point within the P-Q Capability Diagram schematically shown in and defined in Figure 5 below, as measured at the Point of Delivery on CEB side of the Interconnection Boundary: At Maximum Effective Capacity between: 0.95 power factor leading to 0.95 power factor lagging; available from 20% of Maximum Effective Capacity At between 20% Maximum Effective Capacity and 5% Maximum Effective Capacity, MVAR capability to be not less than indicated by straight lines drawn between the requirement at 20% Maximum Effective Capacity and the origin of the plot of MVAR capability against MW output. When operating below 5% Maximum Effective Capacity, there is no Reactive Power capability requirement, however the Facility can only operate within the reactive power tolerance range not exceeding +/-5% of Maximum Effective Capacity; that is within the box in dashed lines in Figure 5.

Related to Phase Unbalance

  • Cut-Off Date Aggregate Principal Balance The Cut-Off Date Aggregate Principal Balance is $ 350,274,594.21.

  • PHASE is a distinct portion of the Work to be provided under this Agreement, as specified in the Statement Of Work.

  • Phase II A small portion of the work for the Phase II modifications to the Plattsburgh Substation will be performed by Transmission Owner, and the remainder will be performed by Clinton and Xxxxxxxxx. A detailed definition of the specific scope for Transmission Owner and Clinton and Xxxxxxxxx including interface points shall be defined during the design phase and, as such documents become available, copies will be delivered to the NYISO, Transmission Owner, Noble Altona Windpark, LLC and Marble River, LLC. The full scope includes the installation of wave traps, CCVT’s and modifications and/or additions to relaying on the MWP-1 and MWP- 2 lines. These lines will be reconfigured at the completion of Phase II to connect to Xxxxx and Xxxxxxx Substations on MWP-1 and the Xxxx Substation on MWP-2. Clinton and Xxxxxxxxx will design the upgrades and purchase the materials based on the outline specification that was prepared and issued by Transmission Owner. The work to be performed by Clinton and Xxxxxxxxx will include both the materials for the exterior and interior installations and items for Transmission Owner installation inside the control building in existing relay panels and communication racks. In addition, Clinton and Xxxxxxxxx will be responsible for the exterior and interior construction work and will provide construction management services in coordination with Transmission Owner. The civil design for the foundations and the electrical design for the cable runs to the control room will be designed by, as approved by Transmission Owner, and installed under the supervision and control of Clinton and Xxxxxxxxx. The equipment will be selected and procured in accordance with the specifications developed during the detailed engineering phase, copies of which shall be furnished to the NYISO, Transmission Owner, Noble Altona Windpark, LLC and Marble River, LLC. The construction of the foundations, structures, wave traps, CCTV and cable runs into the control building to the termination cabinets will be completed by Clinton and Xxxxxxxxx. The work at the Plattsburgh Substation will be installed under Transmission Owner’s CPP-1. Transmission Owner will provide Protection and Controls Engineering, install and terminate wiring from the termination cabinets to the control panels and relays, install relays and equipment in the existing panels, and will commission such work inside the 230kV control building. Transmission Owner will develop the communications protocols and data flow over the circuits.

  • Payment of the balance Within sixty days of completion of the tasks referred to in each order or specific contract, the Contractor shall submit to the Agency a formal request for payment accompanied by those of the following documents, which are provided for in the Special Conditions: ➢ a final technical report in accordance with the instructions laid down in Annex I; ➢ the relevant invoices indicating the reference number of the Contract and of the order or specific contract to which they refer;

  • Project Completion Date It is agreed between the Parties that the Project Completion Date is <END DATE, YEAR>. If the Project is not completed by such date then, subject to an amendment agreed to between the Parties, Alberta Innovates may elect to terminate this Investment Agreement. In such event, Alberta Innovates will notify the Applicant of its decision to terminate as soon as reasonably practical and shall advise the Applicant of the effective date of termination. Alberta Innovates will have no liability or obligation to reimburse the Applicant for any Project Costs incurred after the effective date of termination and may require the Applicant to return any portions of the Investment which were spent on Ineligible Expenses. Additionally, any portion of the Investment not used and accounted for in accordance with this Agreement as of the Project Completion Date or earlier termination is repayable by the Applicant to AI at AI’s request.

  • Phase I In Phase I, the project will be connected as a tap to the Transmission Owner’s 230kV transmission line MWP-2 via one 230kV circuit breaker in series with one of two ring bus breakers for stuck breaker protection (one in each direction) and a tie-line breaker, as shown on the one-line diagram labeled CL-E-IA-01 attached to this Appendix A as Figure 1. The changes to the existing MWP-2 line protection for this arrangement are described in Phase I System Upgrades in Section II of this Appendix A.

  • Phase 2 Phase 2 is expected to consist of Member Nodes and a select number of Nodes operated by non-Members. The non-Member Nodes will be required to comply with Node hosting terms as set forth by the Council, which may be amended from time to time (the “General Node Terms”).

  • Principal Balance Each Receivable had a remaining Principal Balance as of the Cutoff Date of not less than $500.

  • Construction Phase Fee Contractor’s Construction Phase Fee is the maximum amount payable to Contractor for any cost or profit expectation incurred in the performance of the Work that is not specifically identified as being eligible for reimbursement by Owner elsewhere in this Agreement. References in the UGSC to Contractor’s “overhead” and “profit” mean Contractor’s Construction Phase Fee. The Construction Phase Fee includes, but is not limited to, the following items: 9.1 All profit, profit expectations and costs associated with profit sharing plans such as personnel bonuses, incentives, and rewards; company stock options; or any other like expenses of Contractor.

  • Mortgage Loan Liquidated by _________________ (The Company hereby certifies that all proceeds of foreclosure, insurance, condemnation or other liquidation have been finally received and credited to the Collection Account pursuant to the Pooling and Servicing Agreement.)

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!