Application Guide Sample Clauses

Application Guide. You (the applicant organization/agency) are responsible for reading and complying with the instructions included in HRSA’s SF-424 R&R Application Guide, available online at xxxx://xxx.xxxx.xxx/grants/apply/applicationguide/sf424rrguidev2.pdf, except where instructed in this NOFO to do otherwise. A short video explaining the Application Guide is available at xxxx://xxx.xxxx.xxx/grants/apply/applicationguide/.
AutoNDA by SimpleDocs
Application Guide. When the employer determines the job requirement group for the employee, this determination shall be based on the requirements of the employee’s duties. If the employee’s duties include tasks from different job requirement groups, the employee’s job requirement group is determined based on his or her primary duties or by determining a weighted job requirement group for the times spent in duties belonging to different job requirement groups. Using these times requires a task-specific working time record, or if this is not available, a work plan.
Application Guide. In principle, the employer’s consent applies always, except in cases where the absence of work constitutes an unauthorised absence.
Application Guide. RIGID SUBSTATION BUSES The ampacity rating calculations of rigid, Aluminum or Copper, outdoor, exposed non-enclosed buses and conductors involves parameters such as ambient temperature, maximum conductor temperature limitations, wind speed, wind direction, solar gain, emissivity, and absorptivity. The maximum temperature at which the bus can operate is limited by loss of strength (loss of life) due to temperature cycles and mechanical movement due to expansion. Rigid substation bus ratings shall be assigned in accordance with IEEE Standard 605-1998.
Application Guide. SERIES CAPACITORS The impedance, normal rating, long time emergency rating, short time emergency rating, drastic action limit, and short circuit current withstand rating of a series capacitor bank shall be the values provided by the manufacturer or calculated by the owner at 60 Hertz and nominal system voltage e.g. 69 kV, 115 kV, 230 kV or 345 kV consistent with IEEE Standard 824. SHUNT CAPACITORS The kVA rating of a shunt capacitor bank shall be the rating provided by the manufacturer or calculated by the owner at 60 Hertz and nominal system voltage e.g. 69 kV, 115 kV, 230 kV or 345 kV consistent with IEEE Standard 18. SERIES REACTORS The impedance, losses, normal rating, long time emergency rating, short time emergency rating, drastic action limit, and short circuit current withstand rating of a series reactor bank shall be the values provided by the manufacturer or calculated by the owner at 60 Hertz and nominal system voltage e.g. 69 kV, 115 kV, 230 kV or 345 kV consistent with IEEE Standard C57.21. SHUNT REACTORS The kVA rating, losses and impedance of a shunt reactor shall be the values provided by the manufacturer or calculated by the owner at 60 Hertz and nominal system voltage e.g. 69 kV, 115 kV, 230 kV or 345 kV. The impedance of the shunt reactor shall be measured at full voltage as described in IEEE Standard C57.21.
Application Guide. The use of working times in accordance with the work roster is based on the company’s production needs and/or the needs of the employees. The working time in accordance with the work roster refers to shifts, the length of which can vary between four and ten hours. There can be several shifts of varying lengths in a week. The lengths of the shifts can also vary weekly or monthly. The weekly working hours can vary in shifts referred to in the work roster. However, the regular working time shall not exceed 50 hours. The weekly working time must average out at 40 hours in an adjustment period of 52 weeks. This shall be taken into considerations when drawing up rosters.
Application Guide. Circuit Breaker load current ratings shall be calculated as described below at a rated power frequency of 60 Hertz and nominal voltage, e.g. 69 kV, 115 kV, 230 kV or 345 kV. Required fault interrupting capability, rated closing, latching and short-circuit current capability, reclosing capability, interrupting performance and rated transient recovery voltage shall be as specified in Sections 5.8 and 5.9 of ANSI/IEEE Standard C37.04. Current transformers that are part of the circuit breaker installation are normally selected so they will not limit the circuit breaker continuous or emergency ratings. Refer to Appendix H for current transformer rating procedures.
AutoNDA by SimpleDocs
Application Guide. A Guide for the Preparation and Submission of NSF Applications via Xxxxxx.xxx guidelines apply (Note: The NSF Xxxxxx.xxx Application Guide is available on the Xxxxxx.xxx website and on the NSF website at: xxxxx://xxx.xxx.xxx/publications/pub_summ.jsp? ods_key=grantsgovguide).
Application Guide. The rating of an HVDC system (which includes converters, converter transformers, conductors and associated equipment such as filters, switches and busses) is one aspect of its performance protocol, being determined by the facility’s specifications, design and operation. Accordingly, ratings shall be based on information provided by the manufacturer. The rating to be assigned is the Maximum Continuous Capacity, which is the maximum capacity (MW), excluding the added capacity available through means of redundant equipment, for which continuous operation under normal conditions is possible [Reference 1]. Since power flows through an HVDC system are continuously controlled, the LTE, STE and DAL ratings are the same as the Maximum Continuous Capacity.
Application Guide. The kVA rating of a VAR compensator shall be the rating provided by the manufacturer as calculated at 60 Hertz and nominal system voltage e.g. 69 kV, 115 kV, 230 kV or 345 kV.
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!