System Acceptance Test Sample Clauses

System Acceptance Test. 4.10.3.1. TSP shall perform the System Acceptance Test 120 days after completion of the last Operations Test in accordance with the TR Section TP.
AutoNDA by SimpleDocs
System Acceptance Test. 5.4.1 Supplier shall, at no cost to Host, test the System (with respect to the System, a “System Acceptance Test”) to confirm that the System (i) is capable of delivering Solar Services in accordance with the operational requirements that Supplier shall develop and provide to Host (the “System Requirements”) and (ii) meets all requirements established by the Local Distribution Company and any Applicable Law.‌‌
System Acceptance Test. 14 B3708776.6 (a) Nexamp shall, at no cost to Host, test the System (with respect to the System, a “System Acceptance Test”) to confirmthat the System (i) is capable of delivering Solar Services in accordance with the operational requirements that Nexamp shall develop and provide to Host (the “System Requirements”) and (ii) meets all requirements established by the Local Distribution Company and any Applicable Law. Nexamp shall notify Host not less than three (3) days prior to the conducting of System Acceptance Test and Host shall have the right, but not the obligation, to be present at and observe the System Acceptance Test, at no cost to Nexamp. (b) If the results of the System Acceptance Test indicate that the System is capable of delivering electricity generated by the System to Host for four (4) continuous hours using such instruments and meters as have been installed for such purposes and the System has been approved for interconnected operation by the Local Distribution Company, thenNexamp shall send a written notice to that effect to Host (a “Completion Notice”), accompanied by a copy ofthe results of the System Acceptance Test. (c) The “Commercial Operation Date” of the System shall be the tenth (1 0t~~) day after the date ofHost’s receipt of a CompletionNotice for the System. SECTION 6.
System Acceptance Test. The term "
System Acceptance Test. The Contractor shall conduct the System Acceptance Test. The SAT shall include thorough testing of final configurations. The purpose of the SAT is to demonstrate that the equipment was installed correctly and operates at the functional and performance levels required by this SOW and to verify that standards-compliant end-to-end workflows execute as anticipated. SAT shall include systematic end to end testing for local, state, and federal searches, including all response message types.
System Acceptance Test. After the fleet installations have been completed, the System Acceptance Test will be conducted to verify that the entire system is performing as intended. The System Acceptance Test will include the verification of: • Selling • Validation (check in / checkout) • Tests of system behavior under system failure conditions (network failure and SPS/SC failure) • Tests with connections to DriverMate and external interfaces System Acceptance shall not be granted until all previous validation testing of the Smart Card fare system has been completed and a System Acceptance Test is successfully completed. Successful completion of the System Acceptance test will occur if there are no major deficiencies that are recorded by FBC during the System Acceptance test. Minor deficiencies will be recorded onto a punch list and resolved during the warranty period. In the event of any major failure or reoccurring minor failure, system acceptance testing shall be halted until major failure or reoccurring minor failure rectification. FBC may determine after inspection and acceptance that an element is suitable for operation, although it may not be totally responsive to all contract requirements. FBC may conditionally accept that element of the system. Conditionally accepted elements will be available to FBC for use until Trapeze is able to initiate and execute corrective action. Trapeze understands that any conditional acceptance does not remove the liability to correct defects as required by the contract. Any defect will be recorded on a punch list and maintained until the warranty period is completed.
System Acceptance Test. After successful completion of the functional testing the system shall be tested formally with full documentation using the previously approved recording form. The Contractor shall notify the Contracting Officer, in writing, forty eight (48) hours prior to system acceptance testing. The appointed Contracting Officer Representative will witness, date and stamp each test in the procedure. Acceptance of the system will be based upon the written approval of the Contracting Officer Technical Representative.
AutoNDA by SimpleDocs

Related to System Acceptance Test

  • ACCEPTANCE TESTS 11.1 If the Contract provides acceptance tests for Goods and/or the result of Services after their completion and/or delivery to the Purchaser, the acceptance shall only be considered as definitive when such tests have demonstrated the compliance of the Goods and/or the result of the Services to the requirements in the Contract.

  • Acceptance Testing At the time of installation of a LIS trunk group, and at no additional charge, acceptance tests will be performed to ensure that the service is operational and meets the applicable technical parameters.

  • Acceptance/Performance Test 4.7.1 Prior to synchronization of the Power Project, the SPD shall be required to get the Project certified for the requisite acceptance/performance test as may be laid down by Central Electricity Authority or an agency identified by the central government to carry out testing and certification for the solar power projects.

  • INSPECTION, ACCEPTANCE AND REJECTION a. All Goods will be subject to Mercy Corps' inspection and testing (which may be done by a third party authorized by Mercy Corps), at any time and place, including the period of manufacture/production/creation and before final acceptance. If Mercy Corps inspects or tests at Supplier's premises, Supplier, without additional charge, will provide all reasonable facilities and assistance for the safety and convenience of Mercy Corps' inspectors. No inspection or testing done or not done before final inspection and acceptance will relieve Supplier from responsibility for defects or for other failure to meet the requirements of this Agreement. Notwithstanding any prior inspections or payments made, all Goods will be subject to final inspection and acceptance at the Delivery Location within a reasonable time after delivery (but in no event, less than three days after the date of delivery).

  • Technical Specification As enumerated in Special Conditions of Contract/Scope of Work/attached Drawing/ Details/Schedule of Rates.

  • Performance Testing 7.2.1 The Design-Builder shall direct and supervise the tests and, if necessary, the retests of the Plant using Design-Builder’s supervisory personnel and the Air Emissions Tester shall conduct the air emissions test, in each case, in accordance with the testing procedures set forth in Exhibit A (the “Performance Tests”), to demonstrate, at a minimum, compliance with the Performance Guarantee Criteria. Owner is responsible for obtaining Air Emissions Tester and for ensuring Air Emissions Tester’s timely performance. Design-Builder shall cooperate with the Air Emissions Tester to facilitate performance of all air emissions tests. Design-Builder shall not be held responsible for the actions of Owner’s employees and third parties involved in the Performance Testing, including but not limited to Air Emissions Tester.

  • 361 Acceptance of Specified Roads Specified Road work may be accepted subject to completion of clearing work that does not affect the road structure when completion is delayed for reasons beyond control of Purchaser, such as adverse weather. Specified Road work may be accepted subject to completion of planting and seeding for soil stabilization when completion is delayed for reasons beyond control of Purchaser, such as seasonal limitations. Purchaser shall complete planting or seeding on such road during the next suitable planting season. Specified Road work may be conditionally accepted prior to the application of dust palliatives when application is not necessary to prevent dusting of the road surface due to climatic conditions. Purchaser shall apply dust palliative on such roads prior to use during periods when dusting may occur. Prior to request for final inspection, Specified Road work, roadways, borrow pits, and quarries, occupied and no longer needed by Purchaser in connection with Purchaser’s Operations, shall be cleared of all rubbish, excess materials, and temporary structures.

  • Random Testing Notwithstanding any provisions of the Collective Agreement or any special agreements appended thereto, section 4.6 of the Canadian Model will not be applied by agreement. If applied to a worker dispatched by the Union, it will be applied or deemed to be applied unilaterally by the Employer. The Union retains the right to grieve the legality of any imposition of random testing in accordance with the Grievance Procedure set out in this Collective Agreement.

  • Drug Test The compulsory production and submission of urine and/or blood, in accordance with departmental procedures, by an employee for chemical analysis to detect prohibited drug usage.

  • Schematic Design Phase Services § 3.2.1 The Architect shall review the program and other information furnished by the Owner, and shall review laws, codes, and regulations applicable to the Architect’s services.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!