Earthing Sample Clauses

Earthing. Include system to be used (electrodes, counterweights or other), as well as sizes and section of the elements to be used.
AutoNDA by SimpleDocs
Earthing. 33.1 The Service Provider must comply with the earthing requirements set out in the LFC's earthing standards and requirements as published by the LFC on xxx.xxxxxxxxx.xx.xx or otherwise advised by the LFC to the Service provider from time to time.
Earthing. All racks are earthed. The Service Provider is responsible for the provision, installation and maintenance of earthing of all their equipment within the NBI provided Co-Location rack space. NBI will be responsible for earthing the rack.
Earthing. Bonded to earth terminal in normal operation In “island operation” earth mat / rod neutral – earth contractor Generator winding – unearthed Generator winding – star connected Part 3 Annex 4 – Diagram of Customer’s Installation [Include schematic diagram] Part 4Location Plan
Earthing. (i) Measure resistance of each earth well/rod by isolating the same from station grid as well as from other earth well/ rods and when resistance of two earths at a time measure by D.C. drops method.
Earthing. There shall be two independent earthing stations at least 3 meters away from the pump room. The earthing shall consist of an earth tape connected to an independent plate made of C.I. having a conductivity of not less than 100% international standard. All electrical apparatus, cable boxes and sheath/ armour clamps shall be connected to the main bar by means of branch earth connections of appropriate size. All joints in the main bar and branch bar shall have the lapping surface properly tinned to prevent oxidation. The joints shall be revetted and sweathed. Earth plates shall be buried in a pit 1.2 x 1.2 meter a minimum depth of 3 meter below the ground. The connections between the main bars shall be made by means of three 10 mm brass studs and fixed at 100 mm centres. The pit shall filled with coke breeze, rock salt and loose soil. A.G.I.Pipe of 20mm i/d. with perforationon the periphery shall be placed vertically over the plate to reach ground level for watering. A brick masonry manhole 30 x 30 x 30 cm. size shall be provided to surround the pipe for inspection. A bolted removable link connecting main bar outside the pit portion leading to the plate shall be accommodated in this manhole for testing.
AutoNDA by SimpleDocs
Earthing. System Appendix ' c' Page No-4 Supply, installation, commissioning and testing of the earthing system including cost of the following 3 meter long of 5/8"dia tinned copper electrodes. up-to water level including cost of boring and lowering complete with clamp and 2 X 25mm2 stranded copper conductor from copper rod to ground surface in 1-1/2” uPVC Pipe class D with watering cap manhole with cover as per detail complete in all respects. and the resistance should up to 1-3 Ohms. the installation / test should be conducted in presence of engineer inchage. Job 1 44138 4.2
Earthing. The Consumer shall not combine the neutral and protective functions in a single conductor at the Consumer’s installation. The Consumer is advised that the supply voltage, frequency and earthing are subject to the requirements specified by Electricity (Safety, Quality and Continuity) Regulations made by the Gazette Extraordinary No.1975/44 dated 2016.07.13 and any amendment thereto.
Earthing. A main earth bar of G.I shall be provided throughout the full length of the Switch Board with a provision to make connections to earth stations on both sides.