Women’s Toilet Room with Stalls. 1.6.a The toilet room is inaccessible because the sign has no raised or Braille characters and does not have the International Symbol of Accessibility posted at accessible entrances. TR11 24 months 1.6.b The door is inaccessible because it requires 9 pounds of force to open. D3 24 months ATTACHMENT A Please Note: Paragraph 14 of the Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed the facility that is the subject of this Agreement for the purpose of identifying multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment B to this Agreement. In order to ensure that the programs, services, and activities housed in the Rushmore Plaza Civic Center are accessible to persons with disabilities, when viewed in their entirety, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment B to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement.
Women’s Toilet Room with Stalls. 6.4.a. The toilet room is inaccessible because the sign has no raised or Braille characters and is mounted on the door, which has a hold-open device. TR11 6 months
Women’s Toilet Room with Stalls. Attachment J to Settlement Agreement Between the United States of America and Cedar Rapids, Iowa in DJ# 000-00-00
Women’s Toilet Room with Stalls. 4.2.a. The coat hook is inaccessible because it is mounted 65 inches high. TR3 6 months
Women’s Toilet Room with Stalls. 9.14.a. The pull side of the door is inaccessible because it has only 5.5 inches of clear space on the latch side. D5 30 months
Women’s Toilet Room with Stalls. 10.5.a. The facility is inaccessible because, although the facility contains a fire alarm system, there are no visible alarms provided in the toilet room. AL1 6 months
Women’s Toilet Room with Stalls. 1. The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
Women’s Toilet Room with Stalls. (1) The toilet room sign is not accessible. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7. (2) The door is inaccessible because the pressure required to open the door is 9 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
Women’s Toilet Room with Stalls. (1) The toilet room sign is inaccessible. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. (2) There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
Women’s Toilet Room with Stalls. (1) The toilet room sign is inaccessible. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. (2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6. (3) The paper towel dispenser is inaccessible because the controls are mounted at 60 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6. (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4. (5) The lavatory is inaccessible because it has twist controls. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4. (6) The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards § 4.17.3, Fig. 30. (7) The toilet paper dispenser is inaccessible because it is mounted on the opposite the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1 1/2 inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d). (8) The rear grab bar in the designated accessible stall is inaccessible because it is 30 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards § 4...