Sizing Requirements Sample Clauses

Sizing Requirements. 15.19.2.1 Valve Sizing Each valve will be sized to relieve the maximum vapor or liquid load to protect the process system. Process relief loads due to blocked in conditions, reflux failure, cooling water failure, or runaway reactions, shall be obtained form the process material balance flow diagram, adjusted for set pressure conditions. Sizing calculations shall clearly state the basis. Relief loads due to fire, use API RP-520, latest revision, for the heat inputs. Rupture discs shall be sized on the same basis. Relieving pressure or popping pressure shall be at or under the protected equipment design pressure, or maximum working pressure. Set pressure is the difference between relieving pressure and constant back pressure for conventional valves corrected for temperature. For balanced valves, relieving pressure, and set pressure are the same, corrected for temperature. Allowable accumulation is per ASME Boiler and Pressure Vessel Code. For safety valves, the back pressure must be atmospheric. For conventional relief valves, the variation is superimposed back pressure cannot exceed 10 percent of the set pressure. For balanced valves, the variable back pressure cannot exceed 50 percent of the set pressure. Stagger the set pressures when two or more relief valves are used.
AutoNDA by SimpleDocs
Sizing Requirements. The designer shall size the grease interceptor using the “Grease Interceptor Sizing Form” spreadsheet shown at the end of this section and the restaurant types as described below. The following descriptions are to be used to determine the recommended size of a grease interceptor for food preparation and/or food service establishments. To determine the grease interceptor size, consideration must be given to the fat content of the food prepared, number of kitchen drainage fixtures, seating capacity, customer turnover rate, previous problems with the service line or main, compliance history of the food establishment, eat-in or carryout, number of employees, hours of operation, frequency of kitchen use, size of kitchen, number and type of cooking appliances, etc. The food service categories described below function only as a guide. Every food service establishment may not fit clearly within one category; therefore, it may be necessary to combine characteristics and expected size ranges from more than one category to determine the grease interceptor size. • The minimum acceptable volume of a grease interceptor shall not be less than three hundred and twenty-five (325) gallons. (With a dishwasher – 1,000 gallons minimum size) • A copy of the kitchen mechanical or plumbing plan, showing the number of fixtures (3- compartment sink, dishwasher, hand sink, floor drains, etc.) is required to be submitted to the District Manager to confirm the size of the grease interceptor. Facilities often preparing three meals per day or having continuous food prep (cooking) throughout much of the day. These facilities may prepare large amounts of food for distribution to other locations. Examples may include full-service dine-in restaurants, buffets, hotels, large senior-living facilities, hospitals, food courts, grocery stores, caterers, etc. They typically have large or multiple kitchens with a wide range in plumbing fixtures. These facilities frequently have at least one large dishwasher with a large pre-wash sink, vegetable preparation sinks, mop sinks, hand sinks, etc. Food items may be served on disposable or washable dishware. • Expected Size Range of Grease Interceptor: 2,500 – 3,500 gallons Facilities often cooking two meals per day, such as lunch and dinner with washable eating utensils. They usually have a 50 – 150 person seating capacity. Examples may include small senior living facilities, steak houses, gourmet burger establishments, dine-in pizza places, seafood or e...

Related to Sizing Requirements

  • Staffing Requirements Licensee will be in full compliance with the main studio staff requirements as specified by the FCC.

  • Trunking Requirements The Parties will provide designed Interconnection facilities that meet the same technical criteria and service standards, such as probability of blocking in peak hours and transmission standards, in accordance with current industry standards.

  • Forecasting Requirements 19.5.1 The Parties shall exchange technical descriptions and forecasts of their Interconnection and traffic requirements in sufficient detail necessary to establish the Interconnections necessary for traffic completion to and from all Customers in their respective designated service areas.

  • Testing Requirements 12.1. Workplaces - 12.2. On workplaces where the value of the Commonwealth’s contribution to the project that includes the building work is at least $5,000,000, and represents at least 50% of the total construction project value or the Commonwealth’s contribution to the project that includes the building work is at least $10,000,000 (irrespective of its proportion of the total construction project value) the following minimum testing requirements must be adhered to.

  • Monitoring Requirements This Schedule sets out the contract management requirements which are applicable to the delivery of the Services.

  • Funding Requirements If Subrecipient receives funds pursuant to this Contract for more than one program, the funds received by Subrecipient for each program shall be expended only for that program, and Subrecipient shall not expend more funds for any program than are set forth in the Attachment C, Budget Schedule(s) for that program. Subrecipient shall operate continuously throughout the term of this Contract with at least the minimum number and type of staff and volunteers required for provision of the services described. Such staff and volunteers shall be qualified in accordance with all applicable statutes and regulations. Subrecipient agrees to submit to Administrator, upon request, a list of persons, including employees, subcontractors and volunteers, who are to provide such services, and any changes to said list, by name, title, professional degree, and experience.

  • Record Keeping Requirements The Training Provider must make and keep accurate Records for all Training Services in sufficient detail to allow the Department to determine compliance with this Contract (including the accuracy of claims for payment of the Funds).

  • Operating Requirements Any operating and technical requirements that may be applicable due to Regional Transmission Organization, Independent System Operator, control area, or the Connecting Transmission Owner’s requirements, including those set forth in the Small Generator Interconnection Agreement. Operating Requirements shall include Applicable Reliability Standards.

  • Posting Requirements Seller shall post the Development Security in accordance with the following terms and conditions: (i) Seller shall post one-half of the Development Security within thirty

  • Listing Requirements The Company shall not be obligated to deliver any certificates representing any shares until all applicable requirements imposed by federal and state securities laws and by any stock exchanges upon which the shares may be listed have been fully met.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!